| Plan Review Notes For Permit 04020451 |
| Permit Number |
04020451 |
|
| Review Stop |
M |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-04-15 00:00:00 | DENIED: | | | AS PER PREVIOUS COMMENTS PER 2001 FBC(M) | | | 403.3, VENTILATION SYSTEMS OTHER THAN | | | R-3 SHALL BE DESIGNED TO HAVE THE | | | CAPACITY TO SUPPLY MINIMUM OUTDOOR AIR | | | FLOW IN ACCORDANCE WITH TABLE 403.3. | | | | | | PER 2001 FBC(M) 101.4.9, WHERE CODE | | | PROVISIONS CONFLICT WITH A STANDARD, | | | THE CODE PROVISIONS SHALL BE ENFORCED. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|