| Plan Review Notes For Permit 04020451 |
| Permit Number |
04020451 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-27 00:00:00 | DENIED: | | | PLANS INDICATE REFRIGERANT LINES IN A | | | NON-RATED ENCLOSURE.PER ASHRAE 15-92 | | | SECTION 11.12.3 (B), PIPING TO BE | | | CARRIED IN AN APPROVED, RIGID, TIGHT, | | | CONTINUOUS FIRE RESISTING PIPE DUCT OR | | | SHAFT. | | | | | | THE FOLLOWING WAS REVISED WITH THE CODE | | | CHANGE EFFECTIVE JUNE 30, 2003: | | | VENTILIATION SYSTEMS OTHER THAN R-3 | | | (ONE & TWO FAMILY), SHALL HAVE THE | | | MINIMUM REQUIREMENTS FOR OUTSIDE AIR | | | IN ACCORDANCE WITH TABLE 403.3. | | | PLEASE REVISE PLANS TO REFLECT THE | | | CODE CHANGE. | | | | | | PLEASE NOTE, DETAIL FOR THE DRYER BOX | | | IS NOT LEGIBLE.PLEASE PROVIDE | | | MANUFACTURER SUBMITTAL DATA. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|