Plan Review Notes
Plan Review Notes For Permit 04020451
Permit Number 04020451
Review Stop M
Sequence Number 1
Notes
Date Text
2004-02-27 00:00:00DENIED:
 PLANS INDICATE REFRIGERANT LINES IN A
 NON-RATED ENCLOSURE.PER ASHRAE 15-92
 SECTION 11.12.3 (B), PIPING TO BE
 CARRIED IN AN APPROVED, RIGID, TIGHT,
 CONTINUOUS FIRE RESISTING PIPE DUCT OR
 SHAFT.
  
 THE FOLLOWING WAS REVISED WITH THE CODE
 CHANGE EFFECTIVE JUNE 30, 2003:
 VENTILIATION SYSTEMS OTHER THAN R-3
 (ONE & TWO FAMILY), SHALL HAVE THE
 MINIMUM REQUIREMENTS FOR OUTSIDE AIR
 IN ACCORDANCE WITH TABLE 403.3.
 PLEASE REVISE PLANS TO REFLECT THE
 CODE CHANGE.
  
 PLEASE NOTE, DETAIL FOR THE DRYER BOX
 IS NOT LEGIBLE.PLEASE PROVIDE
 MANUFACTURER SUBMITTAL DATA.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE
 CONTACT PATTY KRAUSS AT (561) 805-6719.