2004-02-25 00:00:001) PLEASE SUBMIT PRODUCT APPROVALS
 FOR THE 45 MINUTE FIRE RATED SLIDING
 GLASS DOORS AND THE 45 MINUTE RATED
 FRENCH DOORS. PLEASE PROVIDE
 SELF-CLOSING DEVICE INFORMATION FOR
 THE 45 MINUTE FIRE RATED DOORS.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) ALL NEW FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 4) FIRE ALARM AUDIO AND VISUAL DEVICES
 ARE TO BE INSTALLED IN UNITS DESIGNED
 FOR THE HANDICAP.
  
 5) FDC SHALL BE SINGLE 2 1/2 NOT A
 SINGLE 1 1/2 AS SHOWN ON PLANS.
  