| 2004-02-24 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04020451 |
| | ADD: 735 MALIBU BAY DRBLDG# 9 |
| | CONT: MILLENNIUM |
| | TEL: (305)218-7895 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | PERMIT 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A COPY OF THE VARIANCE, |
| | APPROVED BY THE BOARD OF AJUSTMENT & |
| | APPEAL. 1014.1.1. |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FRENCH DOORS 45 MINUTE FIRE RATING |
| | + APPROVAL FOR WIND 140 MPH WIND |
| | ZONE, RULE 9B-72 STATE APPROVAL |
| | B) SLIDING GLASS DOORS 45 MINUTE FIRE |
| | RATING + APPROVAL FOR WIND, SEE |
| | RULE 9B-72 |
| | C) LOUVER (FUSABLE LINK) RULE 9B-72 |
| | D) ALL TRUSS ANCHORS THAT ARE TO BE |
| | USED, RULE 9B-72 |
| | |
| | 3) THE REPORT SUBMITTED FROM D. V.FRYE- |
| | TEC FOR A 45 MINUTE HORIZONTAL SLIDER |
| | HAS LIMITATIONS LISTED UNDER THE UL LIST |
| | ING REPORT R13157."HORIZONTAL SLIDING |
| | FRAMES SHALL HAVE A MAXIMUM SIZE OF 670 |
| | SQ. IN. WITH A MAXIMUM GLASS LIGHT WIDTH |
| | OF 32 IN. AND HEIGHT OF 42 IN. NOTE A |
| | 32X42= 1344 SQ IN |
| | |
| | 4) INDICATE ON THE FIRE RATED WINDOWS & |
| | DOORS HOW THEY WILL BE SELF CLOSING OR |
| | IF THE FIRE RATED PANEL IS TO BE FIXED |
| | IN PLACE, XO, OX. |
| | |
| | 5) DELETE ALL REFRENCES TO SEMCO TRUSS |
| | ANCHORS, THIS PRODUCT WAS BOUGHT OUT IN |
| | 1999. THERE IS NO STATE LISTING FOR THIS |
| | PRODUCT!!!SHEETS AT1.4, A.DT3 |
| | |
| | 6) REVISION A.DT3 INDICATES THE USE OF |
| | MONIER ROOF TILE VS PRODUCT APPROVAL FOR |
| | ENTEGRA ROOF TILE? |
| | 7) UNITS 9102,9202 & 9302 SHALL ALSO |
| | REQUIRE 45 MIN OPENING PROTECTIVES, |
| | WITHIN 12'-0" OF A PROPERTY LINE. |
| | 705.1.1.2/TABLE 600 NONBEARING WALL |
| | FOOTNOTE "C" AND 1HR PROTECTED. |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |