2004-02-24 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020451
 ADD: 735 MALIBU BAY DRBLDG# 9
 CONT: MILLENNIUM
 TEL: (305)218-7895
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PERMIT 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE A COPY OF THE VARIANCE,
 APPROVED BY THE BOARD OF AJUSTMENT &
 APPEAL. 1014.1.1.
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRENCH DOORS 45 MINUTE FIRE RATING
 + APPROVAL FOR WIND 140 MPH WIND
 ZONE, RULE 9B-72 STATE APPROVAL
 B) SLIDING GLASS DOORS 45 MINUTE FIRE
 RATING + APPROVAL FOR WIND, SEE
 RULE 9B-72
 C) LOUVER (FUSABLE LINK) RULE 9B-72
 D) ALL TRUSS ANCHORS THAT ARE TO BE
 USED, RULE 9B-72
  
 3) THE REPORT SUBMITTED FROM D. V.FRYE-
 TEC FOR A 45 MINUTE HORIZONTAL SLIDER
 HAS LIMITATIONS LISTED UNDER THE UL LIST
 ING REPORT R13157."HORIZONTAL SLIDING
 FRAMES SHALL HAVE A MAXIMUM SIZE OF 670
 SQ. IN. WITH A MAXIMUM GLASS LIGHT WIDTH
 OF 32 IN. AND HEIGHT OF 42 IN. NOTE A
 32X42= 1344 SQ IN
  
 4) INDICATE ON THE FIRE RATED WINDOWS &
 DOORS HOW THEY WILL BE SELF CLOSING OR
 IF THE FIRE RATED PANEL IS TO BE FIXED
 IN PLACE, XO, OX.
  
 5) DELETE ALL REFRENCES TO SEMCO TRUSS
 ANCHORS, THIS PRODUCT WAS BOUGHT OUT IN
 1999. THERE IS NO STATE LISTING FOR THIS
 PRODUCT!!!SHEETS AT1.4, A.DT3
  
 6) REVISION A.DT3 INDICATES THE USE OF
 MONIER ROOF TILE VS PRODUCT APPROVAL FOR
 ENTEGRA ROOF TILE?
 7) UNITS 9102,9202 & 9302 SHALL ALSO
 REQUIRE 45 MIN OPENING PROTECTIVES,
 WITHIN 12'-0" OF A PROPERTY LINE.
 705.1.1.2/TABLE 600 NONBEARING WALL
 FOOTNOTE "C" AND 1HR PROTECTED.
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026