| 2004-02-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04020446 |
| | ADD: 775MALIBU BAY DRBLD# 6 |
| | |
| | PERMIT: 04020447 |
| | ADD: 765 MALIBU BAY DR BLD# 7 |
| | |
| | PERMIT: 04020449 |
| | ADD: 745 MALIBU BAY DRBLD# 8 |
| | |
| | CONT: MILLENNIUM GENERAL CONTRACTOR |
| | TEL: (305)218-7895 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | PERMIT APP/ 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A COPY OF THE VARIANCE, |
| | APPROVED BY THE BOARD OF AJUSTMENT & |
| | APPEAL. 1014.1.1. |
| | |
| | 2) FIRE RATED WINDOWS 45 MIN AT EXTERIOR |
| | STAIRWAY, SEE UL REPORT SUBMITTED FOR |
| | THE D. V. FRYE HORIZONTAL SLIDERS. |
| | LIMITS THE SIZEOF THE "FRAME" HAVING |
| | A LIMITATION OF 670 SQ IN. THE MAXIMUM |
| | GLASS LIGHT WIDTH OF 32 IN AND HEIGHT OF |
| | 42 IN. NOTE 32X42=1344. |
| | |
| | 3) INDICATE ON THE FIRE RATED WINDOWS |
| | NEXT TO THE EXTERIOR STAIRWAY, HOW THEY |
| | WILL BE SELF CLOSING OR IF FIRE RATED |
| | PANEL IS TO BE FIXED IN PLACE, OX.XO. |
| | THE OTHER ISSUE WILL BE THE WINDOWS |
| | LOCATED ON THE ENDS OF THE BUILDINGS |
| | BEING LESS THAN 20' FROM ASSUMED PROP- |
| | ERTY LINES SHALL ALSO REQUIRE 45 MIN |
| | PROTECTIVE OPENINGS. TABLE 600 |
| | TYPE VI- 1HR PROTECTED, BEARING OR NON- |
| | BEARING WALLS. |
| | |
| | 4) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) LOUVER (FUSIBLE LINK) |
| | B) TRUSS ANCHORSRULE 9B-72 |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 5) DELETE ALL REFRENCES TO SEMCO TRUSS |
| | ANCHORS. THIS PRODUCT WAS BOUGHT OUT IN |
| | 1999. THERE WILL BE NO STATE APPROVALS |
| | FOR THIS PRODUCT!!!!!!!!!!!!!!!!! |
| | |
| | 6) REVISION SHEET ADT-3 INDICATES THE |
| | USE OF MONIER ROOF TILE, PRODUCT |
| | APPROVAL IS FOR ENTEGRA ROOF TILE????? |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |