Plan Review Notes
Plan Review Notes For Permit 04020446
Permit Number 04020446
Review Stop B
Sequence Number 1
Notes
Date Text
2004-02-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020446
 ADD: 775MALIBU BAY DRBLD# 6
  
 PERMIT: 04020447
 ADD: 765 MALIBU BAY DR BLD# 7
  
 PERMIT: 04020449
 ADD: 745 MALIBU BAY DRBLD# 8
  
 CONT: MILLENNIUM GENERAL CONTRACTOR
 TEL: (305)218-7895
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PERMIT APP/ 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE A COPY OF THE VARIANCE,
 APPROVED BY THE BOARD OF AJUSTMENT &
 APPEAL. 1014.1.1.
  
 2) FIRE RATED WINDOWS 45 MIN AT EXTERIOR
 STAIRWAY, SEE UL REPORT SUBMITTED FOR
 THE D. V. FRYE HORIZONTAL SLIDERS.
 LIMITS THE SIZEOF THE "FRAME" HAVING
 A LIMITATION OF 670 SQ IN. THE MAXIMUM
 GLASS LIGHT WIDTH OF 32 IN AND HEIGHT OF
 42 IN. NOTE 32X42=1344.
  
 3) INDICATE ON THE FIRE RATED WINDOWS
 NEXT TO THE EXTERIOR STAIRWAY, HOW THEY
 WILL BE SELF CLOSING OR IF FIRE RATED
 PANEL IS TO BE FIXED IN PLACE, OX.XO.
 THE OTHER ISSUE WILL BE THE WINDOWS
 LOCATED ON THE ENDS OF THE BUILDINGS
 BEING LESS THAN 20' FROM ASSUMED PROP-
 ERTY LINES SHALL ALSO REQUIRE 45 MIN
 PROTECTIVE OPENINGS. TABLE 600
 TYPE VI- 1HR PROTECTED, BEARING OR NON-
 BEARING WALLS.
  
 4) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) LOUVER (FUSIBLE LINK)
 B) TRUSS ANCHORSRULE 9B-72
 PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72. SEE
 ATTACHMENT. WWW.FLORIDABUILDING.ORG
  
 5) DELETE ALL REFRENCES TO SEMCO TRUSS
 ANCHORS. THIS PRODUCT WAS BOUGHT OUT IN
 1999. THERE WILL BE NO STATE APPROVALS
 FOR THIS PRODUCT!!!!!!!!!!!!!!!!!
  
 6) REVISION SHEET ADT-3 INDICATES THE
 USE OF MONIER ROOF TILE, PRODUCT
 APPROVAL IS FOR ENTEGRA ROOF TILE?????
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026