| Plan Review Notes For Permit 04020440 |
| Permit Number |
04020440 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-25 00:00:00 | 1) PLEASE SUBMIT PRODUCT APPROVALS FOR | | | THE 45 MINUTE RATED SLIDING GLASS DOORS | | | AND THE 45 MINUTE RATED FRENCH DOORS. | | | PLEASE PROVIDE SELF-CLOSING DEVICE | | | INFORMATION FOR THE 45 MINUTE FIRE | | | RATED DOORS. | | | | | | 2) BUILDING ADDRESS REQUIRED ON PROPER | | | ELEVATION. | | | | | | 3) ALL NEW FIRE ALARM SYSTEMS SHALL BE | | | UL LISTED FOR CENTRAL STATION SERVICE. | | | | | | 4) FIRE ALARM AUDIO AND VISUAL DEVICES | | | ARE TO BE INSTALLED IN UNITS DESIGNED | | | FOR THE HANDICAP. | | | | | | 5) FDC SHALL BE A SINGLE 2 1/2 NOT A | | | SINGLE 1 1/2 AS SHOWN ON THE PLANS. | | | | | | 6) ENTRY DOOR JAMB SHALL BE B LABEL | | | NOT C LABEL AS SHOWN ON ENTRY DOOR | | | HEAD JAMB DETAIL. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|