Plan Review Notes
Plan Review Notes For Permit 04020440
Permit Number 04020440
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-02-25 00:00:001) PLEASE SUBMIT PRODUCT APPROVALS FOR
 THE 45 MINUTE RATED SLIDING GLASS DOORS
 AND THE 45 MINUTE RATED FRENCH DOORS.
 PLEASE PROVIDE SELF-CLOSING DEVICE
 INFORMATION FOR THE 45 MINUTE FIRE
 RATED DOORS.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) ALL NEW FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 4) FIRE ALARM AUDIO AND VISUAL DEVICES
 ARE TO BE INSTALLED IN UNITS DESIGNED
 FOR THE HANDICAP.
  
 5) FDC SHALL BE A SINGLE 2 1/2 NOT A
 SINGLE 1 1/2 AS SHOWN ON THE PLANS.
  
 6) ENTRY DOOR JAMB SHALL BE B LABEL
 NOT C LABEL AS SHOWN ON ENTRY DOOR
 HEAD JAMB DETAIL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910