| 2004-02-25 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04020440 |
| | ADD: 790 MALIBU BAY DR BUILD# 2 |
| | CONT: MILLENNIUM GENERAL CONTRACTOR |
| | TEL: (305)218-7895 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | PERMIT 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A COPY OF THE VARIANCE, |
| | APPROVED BY THE BOARD OF ADJUSTMENT & |
| | APPEAL. 1014.1.1 |
| | |
| | 2) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) FRENCH DOORS 45MIN FIRE RATING PLUS |
| | APPROVAL FOR 140 MPH, RULE 9B-72 |
| | B) SLIDING GLASS DOORS 45 MIN FIRE RAT- |
| | ING PLUS 140 WIND ZONE, RULE 9B-72. |
| | C) LOUVER (FUSIBLE LINK) RULE 9B-72 |
| | D) ALL TRUSS ANCHORS THAT ARE TO BE USED |
| | PROVIDE PROTECT APPROVALS PLUS STATE |
| | APPROVAL, RULE 9B-72 |
| | |
| | 3) THE REPORT SUBMITTED FORM D. V. FRYE- |
| | TEC FOR A 45 MINUTE HORIZONTZL SLIDERS |
| | HAS LIMITATIONS LISTED UNDER THE UL |
| | LISTING REPORT R 13157. A LIMITTATION |
| | OF 670 SQ IN PER PANEL WITH A MAXIMUM |
| | GLASS WIDTH OF 32 IN. AND HEIGHT OF 42IN |
| | NOTE: 32X42= 1344 SQ IN OVER THE 670 |
| | ALLOWABLE!! |
| | |
| | 4) INDICATE ON THE FIRE RATED WINDOWS & |
| | DOORS HOW THEY WILL BE SELF CLOSING OR |
| | IF THE FIRE RATED PANEL IS TO BE FIXED |
| | IN PLACE XO, OX. |
| | |
| | 5) DELETE ALL REFRENCES TO SEMCO TRUSS |
| | ANCHORS, THIS PRODUCT WAS BOUGHT OUT |
| | IN 1999. THERE IS NO STATE LISTING FOR |
| | THESE PRODUCTS!!! SHEET AT.1, A.DT3. |
| | |
| | 6) REVISION A.DT3 INDICATES THE USE OF |
| | MONIER ROOF TILE VS PRODUCT APPROVALS |
| | FOR ENTEGRA ROOF TILE? |
| | |
| | 7) UNITS 2108, 2208 & 2308 WHERE WALLS |
| | ARE LESS THAN 15'-0" FROM THE PROPERTY |
| | LINE WALL OPENINGS WILL BE REQUIRED TO |
| | BE FIRE RATED 705.1.1.2/ TABLE 600 |
| | 1 HR PROTECTED EXT WALL 10'-20' FROM |
| | PROPERTY LINE.************************* |
| | ****TABLE 600 I HR PROTECTED TYPE VI BLD |
| | REQUIRES FOR BEARING OR NON-BEARING |
| | WALLS 10'-20' FROM PROPERTY LINE TO BE |
| | 1 HR RATED/ OPENING PROTECTIVES 45MIN |
| | FOR 40% OPENINGS OR LESS. OVER 40% THE |
| | REMAINDER WOULD NEED TO MEET 1 HR RATING |
| | THIS BUILD IS UNDER THE 40% PERCENT |
| | REQUIRING 45 MIN OPENING PROTECTIVES!!!! |