2004-02-25 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020440
 ADD: 790 MALIBU BAY DR BUILD# 2
 CONT: MILLENNIUM GENERAL CONTRACTOR
 TEL: (305)218-7895
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 PERMIT 1ST REVIEW
 ACTION: DENIED
  
 1) PROVIDE A COPY OF THE VARIANCE,
 APPROVED BY THE BOARD OF ADJUSTMENT &
 APPEAL. 1014.1.1
  
 2) FL BLD CODE 1606.1.5: COMPONENTS &
 CLADDING, PROVIDE 2 COPIES(3 IF THRESH-
 OLD OR RESIDENT INSPECTOR) OF PRODUCT
 TESTING REPORTS,MISSING REPORTS ARE AS
 FOLLOWS:
 A) FRENCH DOORS 45MIN FIRE RATING PLUS
 APPROVAL FOR 140 MPH, RULE 9B-72
 B) SLIDING GLASS DOORS 45 MIN FIRE RAT-
 ING PLUS 140 WIND ZONE, RULE 9B-72.
 C) LOUVER (FUSIBLE LINK) RULE 9B-72
 D) ALL TRUSS ANCHORS THAT ARE TO BE USED
 PROVIDE PROTECT APPROVALS PLUS STATE
 APPROVAL, RULE 9B-72
  
 3) THE REPORT SUBMITTED FORM D. V. FRYE-
 TEC FOR A 45 MINUTE HORIZONTZL SLIDERS
 HAS LIMITATIONS LISTED UNDER THE UL
 LISTING REPORT R 13157. A LIMITTATION
 OF 670 SQ IN PER PANEL WITH A MAXIMUM
 GLASS WIDTH OF 32 IN. AND HEIGHT OF 42IN
 NOTE: 32X42= 1344 SQ IN OVER THE 670
 ALLOWABLE!!
  
 4) INDICATE ON THE FIRE RATED WINDOWS &
 DOORS HOW THEY WILL BE SELF CLOSING OR
 IF THE FIRE RATED PANEL IS TO BE FIXED
 IN PLACE XO, OX.
  
 5) DELETE ALL REFRENCES TO SEMCO TRUSS
 ANCHORS, THIS PRODUCT WAS BOUGHT OUT
 IN 1999. THERE IS NO STATE LISTING FOR
 THESE PRODUCTS!!! SHEET AT.1, A.DT3.
  
 6) REVISION A.DT3 INDICATES THE USE OF
 MONIER ROOF TILE VS PRODUCT APPROVALS
 FOR ENTEGRA ROOF TILE?
  
 7) UNITS 2108, 2208 & 2308 WHERE WALLS
 ARE LESS THAN 15'-0" FROM THE PROPERTY
 LINE WALL OPENINGS WILL BE REQUIRED TO
 BE FIRE RATED 705.1.1.2/ TABLE 600
 1 HR PROTECTED EXT WALL 10'-20' FROM
 PROPERTY LINE.*************************
 ****TABLE 600 I HR PROTECTED TYPE VI BLD
 REQUIRES FOR BEARING OR NON-BEARING
 WALLS 10'-20' FROM PROPERTY LINE TO BE
 1 HR RATED/ OPENING PROTECTIVES 45MIN
 FOR 40% OPENINGS OR LESS. OVER 40% THE
 REMAINDER WOULD NEED TO MEET 1 HR RATING
 THIS BUILD IS UNDER THE 40% PERCENT
 REQUIRING 45 MIN OPENING PROTECTIVES!!!!
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026