Plan Review Notes
Plan Review Notes For Permit 04020434
Permit Number 04020434
Review Stop FIRE
Sequence Number 1
Notes
Date Text
2004-02-26 00:00:001) PLEASE SUBMIT PRODUCT APPROVALS FOR
 THE 45 MINUTE FIRE RATED SLIDING GLASS
 DOORS AND THE 45 MINUTE RATED FRENCH
 DOORS AND EGRESS WINDOWS.
  
 2) BUILDING ADDRESS REQUIRED ON PROPER
 ELEVATION.
  
 3) ALL NEW FIRE ALARM SYSTEMS SHALL BE
 UL LISTED FOR CENTRAL STATION SERVICE.
  
 4) FIRE ALARM AUDIO AND VISUAL DEVICES
 ARE TO BE INSTALLED IN UNITS DESIGNED
 FOR THE HANDICAP.
  
 5) FDC SHALL BE A SINGLE 2 1/2 NOT
 A SINGLE 1 1/2 AS SHOWN ON THE PLANS.
  
 6) ENTRY DOOR JAMB SHALL BE B LABEL
 NOT C LABELED AS SHOWN ON ENTRY DOOR
 HEAD JAMB DETAIL.
  
 MIKE CARSILLO, ASSISTANT FIRE MARSHAL
 835-2910