Plan Review Notes
Plan Review Notes For Permit 04020434
Permit Number 04020434
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-26 00:00:00*** ELECTRICAL PLANS STAMPED, HOWEVER
 E-U2,E-U3 WERE VOIDED DUE TO FIRE
 REVIEW COMMENTS.
  
 REDLINED 250.24, NO EQUIPMENT GROUNDING
 CONDUCTOR FROM METER TO MAIN ON TRASH
 RISER.