| 2004-02-25 00:00:00 | BUILDING PLAN REVIEW TYPE- II-A BLD |
| | PERMIT: 04020434BLD#1 |
| | ADD: 800 MALIBU BAY DR |
| | |
| | PERMIT: 04020443BLD# 3 |
| | ADD: 780 MALIBU BAY DR |
| | |
| | PERMIT:04020444BLD# 4 |
| | ADD: 770 MALIBU BAY DR |
| | |
| | PERMIT: 04020445BLD# 5 |
| | ADD: 760 MALIBU BAY DR |
| | |
| | PERMIT: 04020452BLD# 10 |
| | ADD: 740 MALIBU BAY DR |
| | |
| | PERMIT: 04020454BLD# 11 |
| | ADD: 730 MALIBU BAY DR |
| | |
| | CONT: MILLENNIUM GENERAL CONTRACTOR |
| | TEL: (305)218-7895 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | PERMIT APP/ 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE A COPY OF THE VARIANCE RE- |
| | QUIRED FOR 1014.1.1 BALCONIES, PORCHES |
| | AND GALLERIES, AN APPROVED BY THE BOARD |
| | OF ADJUSTMENT & APPEAL. |
| | |
| | 2) THIS COMMENT APLLIES ONLY TO BLD# 1. |
| | ALTHOUGH THIS BUILDING SETS OVER THE |
| | 15' FROM THE PROPERTY LINE SATISFYING |
| | 705.1.1.2, CLASSIFYING THE BUILD, TYPE |
| | VI 1 HR PROTECTED TABLE 600 FOR WALLS |
| | LOCATED 10'-20' FROM PROPERTY LINE, |
| | OPENING PROTECTIVES REQUIRED 45 MIN FOR |
| | OPENINGS < 40% WALL AREA. |
| | |
| | 3) BUILDINGS 4 & 5 WILL HAVE THE SAME |
| | ISSUE BECAUSE OF THE LOCATION OF THE |
| | GAZEBO.TABLE 600 ASSUMED PROPERTY LINES! |
| | |
| | 4) NOTE THE FIRE RATED TEST REPORT FROM |
| | D. V. FRYE-TEC FOR HORIZONTAL SLIDING |
| | WINDOWS WITH A LIMITATION OF 670 SQ IN |
| | PER FRAME. THE MAXIMUM GLASS LIGHT WIDTH |
| | OF 32"AND HEIGHT OF 42".NOTE 32X42=1344. |
| | |
| | 5) PLEASE INDICATE HOW THE HORIZONTAL |
| | SLIDING UNITS WILL BE SELF CLOSING. |
| | REQUIRED FOR THE < 20' FROM PROPERTY |
| | LINE. |
| | IN CASE OF THE WINDOWS NEXT TO THE |
| | STAIRWAY INDICATE IF A FIXED FIRE RATED |
| | WINDOW OR OTHER MEANS OF CODE COMPLIANCE |
| | |
| | 6) FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) LOUVER |
| | B) TRUSS ANCHORS |
| | PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 7) PLEASE DELETE ALL REFRENCES OF SEMCO |
| | PRODUCTS FROM PLANS, THIS PRODUCT WAS |
| | BOUGHT OUT IN 1999. THERE IS NO STATE |
| | APPROVALS FOR THIS PRODUCT!!!!!!!!!!!!! |
| | |
| | 8) PLANS INDICATE THE USE OF MONIER ROOF |
| | TILE VS SUBMITTING PRODUCT APPROVAL FOR |
| | ENTEGRA ROOF TILE??????????/ |
| | |
| | BUILDING PLAN REVIEW |
| | JIM WITMER |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |