| Plan Review Notes For Permit 04020408 |
| Permit Number |
04020408 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-20 00:00:00 | PROVISO: | | | ADDITIONAL PERMIT REQUIRED FOR THE | | | WALK-IN COOLER.STAND FOR C.U. 2 SHALL | | | COMPLY WITH 2001 FBC 1511.7 FOR THE | | | HEIGHT REQUIREMENT FROM THE ROOF | | | SURFACE TO THE BOTTOM OF THE SUPPORT | | | RAIL (SEE ATTACHED) | | | | | | ADDITIONAL PERMIT REQUIRED FOR HOOD | | | SUPPERSSION.PLANS SUBMITTED WITH | | | BUILDING PERMIT ARE APPROVED. | | | | | | TERMINATION OF EXHAUST FOR GREASE DUCT | | | SHALL BE A MINIMUM OF 10 FT FROM | | | PROPERTY LINES, INTAKE OPENINGS AND | | | PARTS OF THE SAME OR CONTIGUOUS | | | BUILDING PER 2001 FBC(M) 506.3.14.3.A | | | MINIMUM OF 2 FT BETWEEN PARAPET AND | | | VERTICAL DISCHARGE. | | | | | | HOOD PERMIT MAY BE ISSUED WITH BUILDING | | | PERMIT IN LIEU OF HVAC PERMIT.PLAN | | | SHEET H-1 INDICATES NO WORK TO BE DONE | | | ON THE EXISTING A/C. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|