| 2004-02-18 00:00:00 | *************** UNSAT ************** | | | | | | 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN | | | RECEPTS REQ'D TO BE GFI. | | | | | | 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- | | | -ING OF EM/EXT LTS. | | | | | | 3)NOTE: PLEASE SEE 210.62 FOR RECEPTS | | | IN SHOW WINDOWS. | | | | | | 4)NOTE: PLEASE PROVIDE ADDRESS ON TITLE | | | BLOCK. PLEASE ALSO PROVIDE SUITE/ BAY | | | # TO APPLICATION AND FRONT COUNTER STAFF | | | TO ADD TO PERMITS. INSPECTORS WILL NOT | | | BE ABLE TO FIND JOB. | | | NOTE: THERE IS NO "W" NORTHLAKE. JUST | | | NORTHLAKE. | | | | | | 5)NOTE: PLEASE SEE LOADS SHOWN FOR | | | WATER HEATER AND AHU, BOTH SHOWN AS 5KW | | | LOAD W/ 60A AND 50A OCP WITH #6 AWG. | | | PLEASE VERIFY. | | | MAX OCP IS 150% AND MIN IS 125%. | | | 424.3B,422.13 | | | | | | 6)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS | | | FUSES AS BEING MEANS OF OCP. PLEASE | | | VERIFY IF BRKR?? | | | | | | 7)NOTE: PLEASE PROVIDE NOTE ON REQ'D | | | SHUNT TRIP FOR HOOD/ SHUT OFF. | | | NFPA-96 | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|