Plan Review Notes
Plan Review Notes For Permit 04020408
Permit Number 04020408
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-18 00:00:00*************** UNSAT **************
  
 1)NOTE: PLEASE SEE 210.8B3 FOR KITCHEN
 RECEPTS REQ'D TO BE GFI.
  
 2)NOTE: PLEASE SEE 700.12E FOR CIRCUIT-
 -ING OF EM/EXT LTS.
  
 3)NOTE: PLEASE SEE 210.62 FOR RECEPTS
 IN SHOW WINDOWS.
  
 4)NOTE: PLEASE PROVIDE ADDRESS ON TITLE
 BLOCK. PLEASE ALSO PROVIDE SUITE/ BAY
 # TO APPLICATION AND FRONT COUNTER STAFF
 TO ADD TO PERMITS. INSPECTORS WILL NOT
 BE ABLE TO FIND JOB.
 NOTE: THERE IS NO "W" NORTHLAKE. JUST
 NORTHLAKE.
  
 5)NOTE: PLEASE SEE LOADS SHOWN FOR
 WATER HEATER AND AHU, BOTH SHOWN AS 5KW
 LOAD W/ 60A AND 50A OCP WITH #6 AWG.
 PLEASE VERIFY.
 MAX OCP IS 150% AND MIN IS 125%.
 424.3B,422.13
  
 6)NOTE: PLEASE SEE PANEL SCHEDULE, SHOWS
 FUSES AS BEING MEANS OF OCP. PLEASE
 VERIFY IF BRKR??
  
 7)NOTE: PLEASE PROVIDE NOTE ON REQ'D
 SHUNT TRIP FOR HOOD/ SHUT OFF.
 NFPA-96
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]