2005-06-27 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
  
 A. SANITARY RISER DIAGRAM DOES NOT MEET
 CODE REQUIREMENTS, NOR DOES IT REFLECT
 THE FLOOR PLAN. CORRECT THE FOLLOWING:
 1. TRAPS ARE REQUIRED ON THE TUB &
 SHOWER BATH #4. SECTION 1002.1.
 2. RISER SHOWS A TUB AND FLOOR PLAN
 SHOWS A SHOWER. SECTION 104.2.1.
 3. THE WASH MACHINE SHALL CONNECT
 DOWNSTREAM OF THE LAUNDRY SINK ON THE
 STACK, AS THE VERTICAL DRAIN PIPE
 CONNECTING THE TWO FIXTURE DRAINS SHALL
 BE CONSIDERED THE VENT FOR THE LOWER
 FIXTURE. SECTION 908.3
 4. THE WASH MACHINE REQUIRES A MIN. 2'
 STANDPIPE. SECTION 1002.1.
 5. THE CLEANOUT FOR THE WASHMACHINE
 SHALL BE LOCATED 4' ABOVE THE FLOOR.
 SECTION 708.10.
 6. THE WATER CLOSET AND THE BIDET IN
 THE MASTER BATH ARE NOT VENTED. SECTION
 901.2.1.
  