| Plan Review Notes For Permit 04020394 |
| Permit Number |
04020394 |
|
| Review Stop |
P |
| Sequence Number |
5 |
|
| Notes |
| Date |
Text |
| 2005-06-27 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | | | | A. SANITARY RISER DIAGRAM DOES NOT MEET | | | CODE REQUIREMENTS, NOR DOES IT REFLECT | | | THE FLOOR PLAN. CORRECT THE FOLLOWING: | | | 1. TRAPS ARE REQUIRED ON THE TUB & | | | SHOWER BATH #4. SECTION 1002.1. | | | 2. RISER SHOWS A TUB AND FLOOR PLAN | | | SHOWS A SHOWER. SECTION 104.2.1. | | | 3. THE WASH MACHINE SHALL CONNECT | | | DOWNSTREAM OF THE LAUNDRY SINK ON THE | | | STACK, AS THE VERTICAL DRAIN PIPE | | | CONNECTING THE TWO FIXTURE DRAINS SHALL | | | BE CONSIDERED THE VENT FOR THE LOWER | | | FIXTURE. SECTION 908.3 | | | 4. THE WASH MACHINE REQUIRES A MIN. 2' | | | STANDPIPE. SECTION 1002.1. | | | 5. THE CLEANOUT FOR THE WASHMACHINE | | | SHALL BE LOCATED 4' ABOVE THE FLOOR. | | | SECTION 708.10. | | | 6. THE WATER CLOSET AND THE BIDET IN | | | THE MASTER BATH ARE NOT VENTED. SECTION | | | 901.2.1. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|