| Plan Review Notes For Permit 04020394 |
| Permit Number |
04020394 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | | | | 1) NEW SANITARY RISER DIAGRAM DOES NOT | | | MEET CODE REQUIREMENTS | | | A) POWDER ROOM WATER CLOSET IS NOT | | | VENTED. | | | B) SINK IN GARAGE SHALL NOT DRAIN THRU | | | THE BATHROOM FIXTURES. SINK SHALL DIS- | | | CHARGE DOWNSTREAM OF THE BATHROOM FIX- | | | TURES. SECTION 909.1 | | | C) WASHMACHINE AND LAUNDRY SINK DO NOT | | | REFLECT THE FLOOR PLAN. WASH MACHINE IS | | | ON THE RIGHT SIDE AND LAUNDRY SINK IS ON | | | THE LEFT SIDE OF THE STACK. 104.2.1 | | | D) BATH #2 SHOWS TUB ON RISER AND SHOWS | | | A SHOWER ON THE FLOOR PLAN. CLARIFY. | | | E) SIZE ALL PIPES IN BATH #4, 3" REQ'D | | | UP TO SHOWER. TABLE 909.3 | | | F) SEE PIPE SIZING FOR BIDET AND SHOWER | | | IN MASTER BATH. MINIMUM 2" REQUIRED. | | | TABLE 709.1 | | | *********SEE RED LINE CORRECTIONS******* | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|