2004-05-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
  
 1) NEW SANITARY RISER DIAGRAM DOES NOT
 MEET CODE REQUIREMENTS
 A) POWDER ROOM WATER CLOSET IS NOT
 VENTED.
 B) SINK IN GARAGE SHALL NOT DRAIN THRU
 THE BATHROOM FIXTURES. SINK SHALL DIS-
 CHARGE DOWNSTREAM OF THE BATHROOM FIX-
 TURES. SECTION 909.1
 C) WASHMACHINE AND LAUNDRY SINK DO NOT
 REFLECT THE FLOOR PLAN. WASH MACHINE IS
 ON THE RIGHT SIDE AND LAUNDRY SINK IS ON
 THE LEFT SIDE OF THE STACK. 104.2.1
 D) BATH #2 SHOWS TUB ON RISER AND SHOWS
 A SHOWER ON THE FLOOR PLAN. CLARIFY.
 E) SIZE ALL PIPES IN BATH #4, 3" REQ'D
 UP TO SHOWER. TABLE 909.3
 F) SEE PIPE SIZING FOR BIDET AND SHOWER
 IN MASTER BATH. MINIMUM 2" REQUIRED.
 TABLE 709.1
 *********SEE RED LINE CORRECTIONS*******
  