2005-06-15 00:00:00************* UNSAT *************
  
 1)NOTE: PLEASE SEE PLANS SUBMITTED MUST
 BE REVISED BY THE ARCH OF RECORD. PLANS
 MUST BE SIGNED, DATED AND SEALED BY
 ARCH. FS 481.221
 PLANS MUST ALL TITLE BLOCKS AS REQUIRED
 UDNER FAC 61G1-16.004.
  
 2)NOTE: PLEASE SHOW ALL SERVICE
 EQUIPMENT/ PANELS ON PLANS.
 MISSING D, E ETC.
 215.5
  
 3)NOTE: PLEASE SEE 230.72. 225.24 FOR
 GROUPING OF DISCONNECTING MEANS.
 PLEASE SEE GEN SUB PANEL APPEARS TO BE
 SHOWN AS MLO, WHERE ARE MCB IS REQUIRED.
  
 4)NOTE: PLEASE SUBMIT LOAD CALCULATIONS
 ON PANEL SCHEDULES AND FOR SERVICE WHICH
 MEET 2002 NEC 220.31. PLEASE SEE THE
 SAME LOAD OF 41 A'S IS INDICATED AND
 SHOWN ON EACH PANEL LOAD CALC.???
 215.5
  
 5)NOTE: PLEASE SEE EQUIPMENT GROUNDING
 CONDUCTORS SHOWN BEFORE THE FIRST MEANS
 OF DISCONNECT. PLEASE SEE 250.6,250.24
 THESE ARE ONLY INSTALLED AFTER THE FIRST
 MEANS OF DISCONNECT.
  
 6)NOTE: PLEASE SEE MISSING KITCHEN
 COUTERSPACE RECEPT PER 210.52C1
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  