Plan Review Notes
Plan Review Notes For Permit 04020394
Permit Number 04020394
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-23 00:00:00PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FOR PANEL "C" IS #3 ON
 THERISER.IT IS LISTED AS #6 ON PANEL
 SCHEDULE "B". PLEASE CORRELATE
  
 2} PLEASE NOTE THE #6 CONDUCTORS WITH
 100 AMP OCP IS IN VIOLATION OF
 310.16,CKTS 20 & 22, PANEL "B".
  
 3} THE KW RATING FOR PANEL "C" IS LISTED
 @ 20KW IN PANEL "B" AND 18 KW ON PANEL
 "C".PLEASE CORRELATE.
  
 4} NOTE THAT PANEL "B" READS "VA"
 INSTEAD OF "KW".
  
 5} THE REFRIGERATOR IN PANEL "A" IS
 LISTED @ 3KW. THAT WUOLD BE 25 AMPS ON
 THE 20 BREAKER THAT IS SHOWN.
  
 6} THE HEAT STRIPS ON THE MECHANICAL
 PLAN THE ONES ON THE ELECTRICAL PLAN
 ARE NOT THE SAME. PLEASE CORRELATE AND
 RECALCULATE THE LOAD ACCORDINGLY.
  
 7} PLEASE INDICATE THE LOCATION OF "C"
 PANEL.
  
 8} THE DISCONNECT FOR A/C #4 DOES NOT
 COMPLY WITH 110.26 FOR CLEARANCES.
  
 9} PLEASE NOTE THE SPA RECEPTACLE MUST
 BE GFI PER 680.43(A)(1).
  
 10} PLEASE NOTE THAT THE FIRM LICENSE
 NUMBER MUST BE ADDED TO THE TITLE
 BLOCK TO COMPLY WITH 61G1-16.004(2) FAC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026