| 2004-02-23 00:00:00 | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE FEEDER FOR PANEL "C" IS #3 ON |
| | THERISER.IT IS LISTED AS #6 ON PANEL |
| | SCHEDULE "B". PLEASE CORRELATE |
| | |
| | 2} PLEASE NOTE THE #6 CONDUCTORS WITH |
| | 100 AMP OCP IS IN VIOLATION OF |
| | 310.16,CKTS 20 & 22, PANEL "B". |
| | |
| | 3} THE KW RATING FOR PANEL "C" IS LISTED |
| | @ 20KW IN PANEL "B" AND 18 KW ON PANEL |
| | "C".PLEASE CORRELATE. |
| | |
| | 4} NOTE THAT PANEL "B" READS "VA" |
| | INSTEAD OF "KW". |
| | |
| | 5} THE REFRIGERATOR IN PANEL "A" IS |
| | LISTED @ 3KW. THAT WUOLD BE 25 AMPS ON |
| | THE 20 BREAKER THAT IS SHOWN. |
| | |
| | 6} THE HEAT STRIPS ON THE MECHANICAL |
| | PLAN THE ONES ON THE ELECTRICAL PLAN |
| | ARE NOT THE SAME. PLEASE CORRELATE AND |
| | RECALCULATE THE LOAD ACCORDINGLY. |
| | |
| | 7} PLEASE INDICATE THE LOCATION OF "C" |
| | PANEL. |
| | |
| | 8} THE DISCONNECT FOR A/C #4 DOES NOT |
| | COMPLY WITH 110.26 FOR CLEARANCES. |
| | |
| | 9} PLEASE NOTE THE SPA RECEPTACLE MUST |
| | BE GFI PER 680.43(A)(1). |
| | |
| | 10} PLEASE NOTE THAT THE FIRM LICENSE |
| | NUMBER MUST BE ADDED TO THE TITLE |
| | BLOCK TO COMPLY WITH 61G1-16.004(2) FAC. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |