| Date |
Text |
| 2004-03-22 00:00:00 | DENIED |
| | |
| | 1) A RECORDED COPY OF THE NOTICE OF |
| | COMMENCEMENT MUST BE SUBMITTED BEFORE A |
| | PERMIT CAN BE ISSUED. |
| | |
| | 2) IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, PLANS STAMPED BY THEM AND |
| | COPY OF RECEIPT SUBMITTED TO CITY OF |
| | WEST PALM BEACH BUILDING DEPARTMENT, |
| | BEFORE A BUILDING PERMIT CAN BE ISSUED. |
| | |
| | 3) SPECIFY ON PLANS THAT WIRE MESH IN |
| | SLAB IS TO BE SUPPORTED ON APPROVED |
| | MATERIAL AT 3'O.C. PER FBC 1909.3. |
| | |
| | 4) INDICATE THE APPLICABLE ENCLOSURE |
| | CLASSIFICATION AND,IF DESIGNING BY ASCE |
| | 7-98, THE INTERNAL PRESSURE COEFFICENT |
| | PER FBC 1606.1.7. |
| | |
| | 5) SPECIFY THE SIZE OF THE ATTIC |
| | ACCESSES ON THE PLANS. THE MINIMUM SIZE |
| | IS 20 X 36 INCHES PER FBC 2309.6. |
| | |
| | 6) THE A/C AREA LISTED ON THE PLANS DOES |
| | NOT MATCH THE CONDITIONED AREA ON THE |
| | ENERGY CALC. FORM. PLEASE CORRECT. |
| | |
| | 7) SPECIFY THE AREA OF THE COVERED |
| | PORCHES AND GARAGE ON THE AREA CALCS. ON |
| | SHEET A3. |
| | |
| | 8) SPECIFY ON THE PLANS THAT THE DOOR TO |
| | THE GARAGE FROM THE CONDITIONED SPACE IS |
| | INSULATED OR SOLID CORE AS REQUIRED BY |
| | FBC 13-603. |
| | |
| | 9) REVISE THE ROOF SHEATHING FASTENING |
| | SCHEDULE ON A8. FOR A MEAN ROOF HEIGHT |
| | LESS THAN 25'FASTENERS ARE REQUIRED TO |
| | BE SPACED 4"OC AT THE EDGES AND 6"OC |
| | INTERMEDIATE IN ZONE 3 AND FOR A MEAN |
| | ROOF HEIGHT 25'TO 35' FASTENERS ARE |
| | REQUIRED TO BE 8D RING SHANK NAILS |
| | SPACED 4"OC EDGES AND 6"OC INTERMEDIATE |
| | IN ZONE 3. SEE CITY AMENDMENTS TO FBC |
| | TABLE 2306.1. |
| | |
| | 10) IN THE TRUSS ANCHOR SCHEDULE ON A8 |
| | THE (I) HETA 16 W/10- 10D X 1-1/2 NAILS |
| | IS LISTED WITH UPLIFT OF 810#. THE |
| | SIMPSON CATALOG LISTS 1810#. PLEASE |
| | CORRECT. |
| | |
| | 11) SOME OF THE TRUSSES ON THE TRUSS |
| | LAYOUT ON A7 DO NOT HAVE AN ANCHOR |
| | SPECIFIED. PLEASE SPECIFY ANCHORS FOR |
| | ALL TRUSS TO WALL CONNECTIONS. |
| | |
| | 12) PROVIDE A DETAIL OF THE 2X4 FRAME |
| | WALLS AT THE TOWER. SPECIFY THE SPACING |
| | OF THE 2X4S AND STRAPPING REQUIRED TO |
| | ACHIEVE A CONTINOUS LOAD PATH FROM THE |
| | TOWER ROOF TO THE GIRDER TRUSSES BELOW. |
| | |
| | 13) PROVIDE DETAILS AND PRODUCT APPROVAL |
| | FOR THE ANGLED FIXED GLASS WINDOW |
| | ASSEMBLIES AT THE MASTER BATH AND |
| | BREAKFAST/BAR AREA. |
| | |
| | 14) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. |
| | |
| | 15) THE DRAWING SUBMITTED FOR THE CLOPAY |
| | GARAGE DOORS ARE LIMITED TO A MAXIMUM |
| | WIDTH OF 9'. THE DOORS ON THE PLANS ARE |
| | 10' WIDE. SUBMIT APPROPRIATE DRAWINGS. |
| | |
| | 16) SUBMIT MANUFACTURER'S SPECIFICATIONS |
| | AND UL LISTING FOR THE GAS BBQ AND HOOD. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |