Plan Review Notes
Plan Review Notes For Permit 04020394
Permit Number 04020394
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-22 00:00:00DENIED
  
 1) A RECORDED COPY OF THE NOTICE OF
 COMMENCEMENT MUST BE SUBMITTED BEFORE A
 PERMIT CAN BE ISSUED.
  
 2) IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, PLANS STAMPED BY THEM AND
 COPY OF RECEIPT SUBMITTED TO CITY OF
 WEST PALM BEACH BUILDING DEPARTMENT,
 BEFORE A BUILDING PERMIT CAN BE ISSUED.
  
 3) SPECIFY ON PLANS THAT WIRE MESH IN
 SLAB IS TO BE SUPPORTED ON APPROVED
 MATERIAL AT 3'O.C. PER FBC 1909.3.
  
 4) INDICATE THE APPLICABLE ENCLOSURE
 CLASSIFICATION AND,IF DESIGNING BY ASCE
 7-98, THE INTERNAL PRESSURE COEFFICENT
 PER FBC 1606.1.7.
  
 5) SPECIFY THE SIZE OF THE ATTIC
 ACCESSES ON THE PLANS. THE MINIMUM SIZE
 IS 20 X 36 INCHES PER FBC 2309.6.
  
 6) THE A/C AREA LISTED ON THE PLANS DOES
 NOT MATCH THE CONDITIONED AREA ON THE
 ENERGY CALC. FORM. PLEASE CORRECT.
  
 7) SPECIFY THE AREA OF THE COVERED
 PORCHES AND GARAGE ON THE AREA CALCS. ON
 SHEET A3.
  
 8) SPECIFY ON THE PLANS THAT THE DOOR TO
 THE GARAGE FROM THE CONDITIONED SPACE IS
 INSULATED OR SOLID CORE AS REQUIRED BY
 FBC 13-603.
  
 9) REVISE THE ROOF SHEATHING FASTENING
 SCHEDULE ON A8. FOR A MEAN ROOF HEIGHT
 LESS THAN 25'FASTENERS ARE REQUIRED TO
 BE SPACED 4"OC AT THE EDGES AND 6"OC
 INTERMEDIATE IN ZONE 3 AND FOR A MEAN
 ROOF HEIGHT 25'TO 35' FASTENERS ARE
 REQUIRED TO BE 8D RING SHANK NAILS
 SPACED 4"OC EDGES AND 6"OC INTERMEDIATE
 IN ZONE 3. SEE CITY AMENDMENTS TO FBC
 TABLE 2306.1.
  
 10) IN THE TRUSS ANCHOR SCHEDULE ON A8
 THE (I) HETA 16 W/10- 10D X 1-1/2 NAILS
 IS LISTED WITH UPLIFT OF 810#. THE
 SIMPSON CATALOG LISTS 1810#. PLEASE
 CORRECT.
  
 11) SOME OF THE TRUSSES ON THE TRUSS
 LAYOUT ON A7 DO NOT HAVE AN ANCHOR
 SPECIFIED. PLEASE SPECIFY ANCHORS FOR
 ALL TRUSS TO WALL CONNECTIONS.
  
 12) PROVIDE A DETAIL OF THE 2X4 FRAME
 WALLS AT THE TOWER. SPECIFY THE SPACING
 OF THE 2X4S AND STRAPPING REQUIRED TO
 ACHIEVE A CONTINOUS LOAD PATH FROM THE
 TOWER ROOF TO THE GIRDER TRUSSES BELOW.
  
 13) PROVIDE DETAILS AND PRODUCT APPROVAL
 FOR THE ANGLED FIXED GLASS WINDOW
 ASSEMBLIES AT THE MASTER BATH AND
 BREAKFAST/BAR AREA.
  
 14) PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 15) THE DRAWING SUBMITTED FOR THE CLOPAY
 GARAGE DOORS ARE LIMITED TO A MAXIMUM
 WIDTH OF 9'. THE DOORS ON THE PLANS ARE
 10' WIDE. SUBMIT APPROPRIATE DRAWINGS.
  
 16) SUBMIT MANUFACTURER'S SPECIFICATIONS
 AND UL LISTING FOR THE GAS BBQ AND HOOD.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714