| 2004-02-19 00:00:00 | |
| | DENIED |
| | ~~~~~~ |
| | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~ |
| | PLEASE MAKE THE FOLLOWING CORRECTIONS |
| | FOR CODE COMPLIANCE AND RESUBMIT FOR |
| | REVIEW. |
| | |
| | 1} THE FEEDER FROM THE DISCONNECT TO |
| | THEMETER NEEDS A GROUND WIRE TO COMPLY |
| | WITH 250.122. |
| | |
| | 2} PLEASE INDICATE THE LOCATION OF THE |
| | SERVICE EQUIPMENT ON THE PLAN. |
| | |
| | 3} THE RECEPTACLE IN THE MASTER BATH |
| | DOES NOT COMPLY WITH 210.52(D),MUST BE |
| | WITHIN 3'. |
| | |
| | 4} BATH #2 NEEDS A SECOND RECEPTACLE TO |
| | COMPLY WITH 210.52(D). |
| | |
| | 5} A SMOKE DETECTOR MUST BE ADDED |
| | OUTSIDE DEN/BEDROOM #3 TO COMPLY WITH |
| | 8-1.4.1.6.2 NFPA-72. |
| | |
| | 6} THERE MUST BE A SMOKE DETECTOR |
| | "OUTSIDE" THE DOORS ENTERING THE HALL |
| | TO THE MASTER SUITE. THE DETECTOR IN |
| | THE HALL IS NOT "OUTSIDE" BY DEFINITION |
| | BECAUSE THERE IS NO DOOR IN THE ARCH |
| | LEADING INTO THE BEDROOM. |
| | |
| | 7} PLEASE SEE NOTE #16 SHEET C-1, ELEC. |
| | NOTES, REFERS TO SMOKE DETECTORS BEING |
| | FED FROM KITCHEN OR BATH LIGHTING. THIS |
| | IS ACCEPTABLE PER CODE, BUT THOSE |
| | CIRCUITS WOULD HAVE TO BE ON AN ARC |
| | FAULT BREAKER FOR THE DETECTORS LOCATED |
| | INSIDE THE BEDROOMS TO COMPLY WITH |
| | 210.12. |
| | |
| | 8} SEE NOTE #16 AND THE REFERENCE TO ARC |
| | FAULT FOR ALL"DWELLING ROOM RECEPTCLES" |
| | TO BE SURE THIS INDICATES THE ARCHITECTS |
| | INTENT. |
| | |
| | IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| | |
| | BILL TROBAUGH |
| | ELECTRICAL PLAN REVIEW |
| | 561/805-6718 |
| | [email protected] |