2004-02-19 00:00:00 
 DENIED
 ~~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} THE FEEDER FROM THE DISCONNECT TO
 THEMETER NEEDS A GROUND WIRE TO COMPLY
 WITH 250.122.
  
 2} PLEASE INDICATE THE LOCATION OF THE
 SERVICE EQUIPMENT ON THE PLAN.
  
 3} THE RECEPTACLE IN THE MASTER BATH
 DOES NOT COMPLY WITH 210.52(D),MUST BE
 WITHIN 3'.
  
 4} BATH #2 NEEDS A SECOND RECEPTACLE TO
 COMPLY WITH 210.52(D).
  
 5} A SMOKE DETECTOR MUST BE ADDED
 OUTSIDE DEN/BEDROOM #3 TO COMPLY WITH
 8-1.4.1.6.2 NFPA-72.
  
 6} THERE MUST BE A SMOKE DETECTOR
 "OUTSIDE" THE DOORS ENTERING THE HALL
 TO THE MASTER SUITE. THE DETECTOR IN
 THE HALL IS NOT "OUTSIDE" BY DEFINITION
 BECAUSE THERE IS NO DOOR IN THE ARCH
 LEADING INTO THE BEDROOM.
  
 7} PLEASE SEE NOTE #16 SHEET C-1, ELEC.
 NOTES, REFERS TO SMOKE DETECTORS BEING
 FED FROM KITCHEN OR BATH LIGHTING. THIS
 IS ACCEPTABLE PER CODE, BUT THOSE
 CIRCUITS WOULD HAVE TO BE ON AN ARC
 FAULT BREAKER FOR THE DETECTORS LOCATED
 INSIDE THE BEDROOMS TO COMPLY WITH
 210.12.
  
 8} SEE NOTE #16 AND THE REFERENCE TO ARC
 FAULT FOR ALL"DWELLING ROOM RECEPTCLES"
 TO BE SURE THIS INDICATES THE ARCHITECTS
 INTENT.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026