Plan Review Notes
Plan Review Notes For Permit 04020383
Permit Number 04020383
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-09 00:00:00DENIED
  
 1) THE PLAN REVIEW NUMBER ON THE COPY OF
 THE PAID RECIEPT DOES NOT MATCH THE
 PLAN REVIEW NUMBER ON THE PLANS. SUBMIT
 THE CORRECT PAID RECIEPT.
  
 2) SPECIFY THE BOTTOM CORD LIVE LOAD ON
 THE PLANS. FBC TABLE 1604.1 REQUIRES
 ATTICS WITHOUT STORAGE TO HAVE A LIVE
 LOAD OF 10 PSF AND 30 PSF FOR ATTICS
 WITH STORAGE.
  
 3) REVISE THE SLIDING GLASS DOOR BUCK
 DETAIL ON A4 TO STATE THAT THEY ARE
 FASTENED THROUGH THE BUCK AND NOT TO IT.
 SEE FBC 1707.4.4.2.
  
 4) THE HEIGHTS LISTED FOR THE MASONRY
 OPENINGS OF WINDOWS 12 AND 13 ON A4 ARE
 INCORRECT (SHOULD BE 64"). PLEASE
 REVISE.
  
 5) UPDATE THE SEMCO TRUSS HANGER
 SPECIFIED IN DETAIL 9 ON A5 TO A CURRENT
 ANCHOR WITH STATE OR LOCAL PRODUCT
 APPROVAL.
  
 6)PRODUCT APPROVALS SUBMITTED WITH
 PERMIT APPLICATION AFTER OCTOBER 1, 2003
 ARE REQUIRED TO COMPLY WITH THE FLORIDA
 PRODUCT APPROVAL SYSTEM. FOR INFORMATION
 PLEASE SEE THE STATE WEBSITE AT
 WWW.FLORIDABUILDING.ORG. PRODUCTS WITH
 STATEWIDE APPROVAL ARE REQUIRED TO BE
 SUBMITTED WITH A COVER SHEET THAT LISTS
 THE PRODUCT IDENTITY NUMBER FROM THE
 STATE. IF THE PRODUCT DOES NOT HAVE
 STATEWIDE APPROVAL, SUBMIT AN APPLICA-
 TION FOR LOCAL PRODUCT APPROVAL OR SITE
 SPECIFIC FORM PER RULE 9B-72.
  
 7) SPECIFY ON THE PLANS THAT THE DOOR
 FROM THE GARAGE TO THE CONDITIONED SPACE
 IS INSULATED OR SOLID CORE AS REQUIRED
 BY FBC CHAPTER 13 SECTION 603.
  
 8) SUBMIT PRODUCT APPROVALS FOR THE 16'
 LONG MULLION BETWEEN THE SLIDING GLASS
 DOOR AND THE TRANSOM AT THE GREAT ROOM.
 THE ONE SUBMITTED ONLY LISTS UP TO A 12'
 MULL LENGTH.
  
 ROBERT MCDOUGAL
 BLDG. PLAN REVIEW
 (561)805-6714