| Plan Review Notes For Permit 04020367 |
| Permit Number |
04020367 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-06 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04020367 | | | ADD: 2151 45TH ST# 209 | | | CONT: MIKE MOORE CONST | | | TEL: (561)262-6605 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) PLEASE PROVIDE A COMPLETE FLOORPLAN | | | TO SEE IF THE 2 EXISTS PROVIDED MEET | | | THE 1/2 THE DIAGONAL FOR EXISTING. IS | | | THE BUILDING FIRESPRINKLERED? | | | | | | 2) PROVIDE ADD INFO FOR THE (2) EGRESS | | | DOORS, ARE THEY FIRE RATED AND DO THEY | | | HAVE CLOSERS? | | | | | | 3) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY. | | | | | | 4) THE BREAK ROOM SINK MUST MEET THE | | | FL ACCESSIBILITY CODE 11-4.24 (1-7) | | | | | | 5)704.2.1.4 CORRIDOR PARTITIONS, SMOKE | | | STOP PARTITIONS, HORIZONTAL EXIT PART- | | | ITIONS, EXIT ENCLOSURES, AND FIRE | | | RATED WALLS REQUIRED TO HAVE PROTECTED | | | OPENINGS SHALL BE EFFECTIVELY AND | | | PERMANETLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE | | | AUTHORITY HAVING JURISDICTION. SUCH IDEN | | | TIFICATION SHALL BE ABOVE ANY DECORATIVE | | | CEILING CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING" FIRE & SMOKE BARRIER | | | PROTECT ALL OPENINGS". | | | | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|