| 2004-02-23 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 BUILDING |
| | FBC-2001 CHAPTER 11 |
| | |
| | 1) ORIGINAL PERMIT APPLICATION REQUIRED. |
| | COPIES OF SIGNATURES, NOTARY SEAL ECT |
| | NOT ACCEPTABLE. |
| | 2) SHOW CLEAR FLOOR SPACE FOR ALL |
| | ACCESSIBLE FIXTURES PER 11-4.15.5, 11-4. |
| | 16.2, 11-4.18.3, 11-4.19.3, 11-4.22.3, |
| | AND 11-4.24.5. |
| | 3) SHOW URINAL HEIGHT PER 11-4.18.2. |
| | (SEE 11-4.22.5). |
| | 4) SHOW LOUNGE, #107 DETAIL #7 SHT A-7.1 |
| | KNEE CLEARANCE 11-4.24.3, DEPTH 11-4.24. |
| | 4, & EXPOSED PIPES & SURFACES 11-4.24.6. |
| | 5) AN RPZ BACKFLOW IS REQUIRED ON WATER |
| | SERVICE TO BLDG. 608.13.2 |
| | 6) INFORMATIONAL - SEPARATE IRRIGATION |
| | PERMIT IS REQUIRED. |
| | 7) SHT P0.1 WATER HEATER DETAIL, THERMAL |
| | EXPANSION CONTROL IS REQUIRED 607.3.2. - |
| | DIELECTRIC UNIONS NOT APPROVED FOR WATER |
| | USE, DELETE FROM DETAIL. (SEE PLUMBING |
| | NOTE #14). |
| | 8) SHT P0.1 WATER HEATER DETAIL, PROVIDE |
| | INFORMATION FROM ENGINEER TO SHOW THAT |
| | POINT LOADING OF WATER HEATER ON BOTTOM |
| | CORD OF JOISTS HAS BEEN ADDRESSED. SEC |
| | 1603.3. (APPROX. 300 LBS.). |
| | 9) SHT P2.1 STATES "CONNECT TO EXISTING |
| | WATER & SEWER" PLEASE CLAIRFY. |
| | 10) SHT P4.1 CENTER ROOF, - ROOF DRAIN |
| | CALLS OUT 8,000 SF, BUT OVERFLOW DRAIN |
| | ONLY INDICATES 2500 SF. PLEASE CLAIRFY. |
| | SECTION 104.2.1 |
| | 11) SUBMIT A STORM RISER DIAGRAM. SHOW |
| | ALL PIPE SIZING AND INDICATE TERMINATION |
| | OF PIPE. 104.3.1.1 |
| | 12) SHT P4.1 ROOF PIPING SUPPORT DETAIL |
| | FOR CONDENSATE, IS THE CONCRETE STEPPING |
| | STONES ON THE ROOF AN ENGINEERED SYSTEM |
| | THAT WILL WITHSTAND 140 MPH WIND SPEED? |
| | INDICATE HOW STONES WILL BE ATTACHED TO |
| | THE ROOF. INDICATE HOW SLOPE WILL BE |
| | MAINTAINED FROM ROOF UNITS TO ROOF DRAIN |
| | 13) SHT P4.1 ROOF PIPING SUPPORT DETAIL |
| | FOR CONDENSATE, DETAIL INDICATES STONES |
| | TO BE 6'0" ON CENTER, TABLE 308.5 STATES |
| | 4'0" MAX FOR PVC PIPE HORIZONTAL SPACING |
| | PLEASE CLAIRFY. |
| | 14) PVC EXPOSED TO UV LIGHT RAYS FROM |
| | THE SUN SHALL BE PAINTED WITH AN APPROV- |
| | ED PAINT. (NON OIL BASE) |
| | 15) SHT P5.1 DOMESTIC WATER ISOMETRIC, |
| | WATER HAMMER ARRESTORS SHALL BE LOCATED |
| | NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" |
| | NOT IN THE CEILING AS SHOWN. PDI-WH 201 |
| | AND MANUF. INSTALLATION INSTRUCTIONS. |
| | (SEE PLUMBING NOTE #13 SHT P0.1) |
| | |