| Plan Review Notes For Permit 04020363 |
| Permit Number |
04020363 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-25 00:00:00 | DENIED: | | | 1.PLEASE CLARIFY NOTE ON PLANS SHEET | | | M2.1, ALL OPEN DUCTS TO BE COVERED WITH | | | STAINLESS WIRE MESH.WILL THIS BE A | | | FINISHED PRODUCT OR FOR FUTURE?EXPLAIN | | | RATIONAL FOR NOT INSTALLING A GRILLE. | | | | | | 2.FAN SHUTDOWN BY DUCT SMOKE DETECTORS | | | SHALL HAVE NOTIFICATION TO ALARM/STROBE | | | IN NORMALLY OCCUPIED AREAS. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE | | | CONTACT PATTY KRAUSS AT (561) 805-6719. |
|