| Plan Review Notes For Permit 04020363 |
| Permit Number |
04020363 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-13 00:00:00 | 1) SEPARATE PLANS AND PERMITS REQUIRED | | | FOR THE FIRE ALARM SYSTEM. FIRE | | | ALARM SYSTEM SHALL BE UL LISTED FOR | | | CENTRAL STATION SERVICE. A CERTIFICATE | | | FOR CENTRAL STATION SERVICE SHALL | | | BE PROVIDED AT TIME OF FIRE ALARM | | | PERMIT APPLICATION. | | | | | | 2) NOTES ON PAGE FAO.1. ARE INCORRECT. | | | NOTES 17 AND 18 ARE TO BE REVISED. | | | | | | 3) A KNOX-BOX WILL BE REQUIRED. | | | | | | 4) NO EXIT SIGN PRESENT DIRECTLY IN | | | FRONT OF LOUNGE DOOR TO DIRECTING | | | PERSON TO THE LOUNGE EXTERIOR EXIT. | | | | | | 5) BUILDING ADDRESS NOT SHOWN ON | | | ELEVATION DRAWING. BUILDING ADDRESS | | | SHALL BE A MINIMUM OF 6" HIGH. | | | | | | 6) TENANT SPACE B IS TO BE FIRE | | | SPRINKLER PROTECTED WHEN SPACE A IS. | | | | | | 7) NO FIRE SPRINKLER PLANS PROVIDED. | | | | | | 8) PLEASE INDICATE INTERIOR FINISH | | | CLASSIFICATION FOR WALLS AND CEILINGS. | | | | | | 9) PLEASE PROVIDE A LIFE SAFETY | | | PLAN FOR REVIEW. | | | | | | MIKE CARSILLO, ASSISTANT FIRE MARSHAL | | | 835-2910 |
|