| Date |
Text |
| 2004-03-08 00:00:00 | BUILDING PLAN REVIEW |
| | PERMIT: 04020363 |
| | ADD: 1720 CENTERPARK DRIVE EAST |
| | CONT: THE WEITZ CO |
| | TEL: (561)686-5511 |
| | FL BLD CODE= 2001 FLORIDA BUILDING CODE |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PROVIDE NOC RECORDED WITH THE CLERK |
| | OF COURT BEFORE A PERMIT CAN BE ISSUED. |
| | |
| | 2) PROVIDE FLOOD ZONE ELEVATION |
| | CERTIFICATE FOR NEW CONSTRUTION WITH |
| | BASE FLOOD ELEVATION, CITY CODE |
| | REQUIRESAN ADDITIONAL 6". LOCATED IN A |
| | "A9" |
| | MINIMUM ELEVATION REQUIRED IS 13'-6". |
| | |
| | 3) FL BLD CODE 1804.2.2 QUESTIONABLE |
| | SOILS, WHERE THE BEARING CAPACITY IS |
| | NOT DEFINETLY KNOWN OR IS IN QUESTION. |
| | WHERE THE BEARING CAPACITY OF THE SOIL |
| | IS NOT DEFINITEY KNOWN, OR IS IN |
| | QUESTIONTHE BUILDING OFFICIAL MAY |
| | REQUIRE EXPLORATIONS, TEST OR OTHER |
| | ADEQUATE PROOF AS TO THE PERMISSIBLE |
| | SAFE BEARING |
| | CAPACITY. REQUIRED TEST AND RECOMMENDA- |
| | TIONS SUBMITTED TO VERIFY BEARING CAPA- |
| | CITY SHALL BE CERTIFIED BY A GEOTECH- |
| | NICALREPORT FROM A DESIGN PROFESSIONAL |
| | PROPERLY LICENSED IN THE STATE OF |
| | FLORIDA. |
| | |
| | 4) TABLE 500 ISSUES THE AREA INCREASE |
| | TAKEN FOR FIRE SPRINKLERED BUILDINGS, |
| | PROVIDE FIRESPRINKLER PLANS BEFORE ISSUA |
| | NCE OF PERMIT. |
| | |
| | 5) PLANS DO NOT INDICATE THE OPEN WORK |
| | STATIONS, INDICATE LOCATION OF WORK |
| | STATIONS, EGRESS AISLES AND THE COMMON |
| | PATH FROM ROOM 114, NOT TO EXCEED 75'. |
| | |
| | 6) 11-4.30.1 SIGNAGE REQUIRED TO BE |
| | ACCESSIBLE BY 11-4.1 SHALL COMPLY WITH |
| | APPLICABLE PROVISIONS OF 11-4.30. |
| | |
| | 7) THE EXITS AT 103-B & 136-B BOTH ARE |
| | PART OF REQUIRED EXITS, AND ACCESSIBLE |
| | EXITS REQUIRED TO GO TO THE PUBLIC WAY |
| | MEANS OF EGRESS. DEFINTIONS CHAP2, CHAP- |
| | TER 11-3.5 DEFINITIONS. SIDEWALKS TO BE |
| | A MINIMUM OF 44" REQUIRED MEANS OF |
| | EGRESS. |
| | |
| | 8)1204.2 SURROUNDING MATERIALS; |
| | THE WALLS & FLOORS OF ALL PUBLIC REST- |
| | ROOMS SHALL BE LINED WITH NONABSORBANT |
| | MATERIALS TO A HEIGTH OF 4'-0" ABOVE THE |
| | FLOOR. |
| | |
| | 9)1511.7 ROOF MOUNTED MECHANICAL UNIT |
| | S SHALL BE MOUNTED ON CURBS RAISED A |
| | MINIMUM OF 8 INCHES ABOVE THE ROOF SUR- |
| | FACE, OR WHERE ROOFING MATERIALS EXTEND |
| | BENEATH THE UNIT, ON RAISED EQUIPMENT |
| | SUPPORTS PROVIDING A MINIMUM CLEARENCE |
| | HEIGHT IN ACCORDANCE WITH TABLE 1511.7. |
| | MECH. 301.13 WIND RESISTANCE |
| | MECHANICAL EQUIPMENT, APPLIANCES AND SUP |
| | PORTS THAT ARE EXPOSED TO WIND SHALL BE |
| | DESIGNED AND INSTALLED TO RESIST THE |
| | WIND PRESSURES ON THE EQUIPMENT & THE |
| | SUPPORTS AS DETERMINED IN ACCORDANCE |
| | WITH THE FL BLD CODE. THIS MAY BE ACCOMP |
| | LISHED BY DESIGN OR BY APPLICATION OF |
| | SECTION 301.13.1. |
| | SHEET S-5 A/C SUPPORT DETAILS DO NOT |
| | INDICATE THE ATTACHMENT OF THE CURB, |
| | 8" IN HEIGHT ABOVE THE ROOF DECK. |
| | |
| | 10)FL BLD CODE 1606.1.5: COMPONENTS & |
| | CLADDING, PROVIDE 2 COPIES(3 IF THRESH- |
| | OLD OR RESIDENT INSPECTOR) OF PRODUCT |
| | TESTING REPORTS,MISSING REPORTS ARE AS |
| | FOLLOWS: |
| | A) WINDOWS |
| | B) MULLIONS |
| | C) EXTERIOR DOORS |
| | D) ROOFING ASSEMBLIES |
| | E) STORM SHUTTERS IF IMPACT GLAZING |
| | NOT PROVIDED. |
| | ***********IMPORTANT***************** |
| | 11) PRODUCT APPROVALS SUBMITTED WITH |
| | PERMIT APPLICATION AFTER OCTOBER 1, 2003 |
| | ARE REQUIRED TO COMPLY WITH THE FLORIDA |
| | PRODUCT APPROVAL SYSTEM. FOR INFORMATION |
| | PLEASE SEE THE STATE WEBSITE AT |
| | WWW.FLORIDABUILDING.ORG. PRODUCTS WITH |
| | STATEWIDE APPROVAL ARE REQUIRED TO BE |
| | SUBMITTED WITH A COVER SHEET THAT LISTS |
| | THE PRODUCT IDENTITY NUMBER FROM THE |
| | STATE. IF THE PRODUCT DOES NOT HAVE |
| | STATEWIDE APPROVAL, SUBMIT AN APPLICA- |
| | TION FOR LOCAL PRODUCT APPROVAL OR SITE |
| | SPECIFIC FORM PER RULE 9B-72. SEE |
| | ATTACHMENT. WWW.FLORIDABUILDING.ORG |
| | |
| | 12)BEFORE A PERMIT TO CONSTRUCT, MAY |
| | BE ISSUED, IMPACT FEES MUST BE PAID TO |
| | PALM BEACH COUNTY. THE ACTUAL PERMIT |
| | SET OF PLANS MUST BE STAMPED BY THAT |
| | OFFICE, AND A COPY OF THE PAID RECEIPT |
| | ATTACHED TO THE PERMIT APPLICATION. |
| | PLEASE CALL (561)233-5025 FOR MORE |
| | INFORMATION. |
| | |
| | LOOK FOR COMMENTS BY THE OTHER PLAN |
| | REVIEW DISCIPLINES THAT MAY BE WRITTEN |
| | ON THE APPLICATION, PLANS, OR ATTACHED |
| | SEPARATELY. WHEN RESUBMITTING PLANS |
| | PLEASE CLEARLY INDICATE THE REVISION AND |
| | REMOVE AND REPLACE ANY PAGES AS NECESS- |
| | ARY. SUBMIT (1) SET OF OLD DRAWINGS WITH |
| | THE PLANS WHEN RESUBMITTING PLANS. A |
| | TRANSMITTAL LETTER LISTING THE ORIGINAL |
| | REVIEW NUMBER, WITH A DESCRIPTION OF THE |
| | REVISION MADE, IDENTIFYING THE SHEET OR |
| | SPECIFICATION PAGE WHERE THE CHANGES CAN |
| | BE FOUND, WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED |
| | COOPERATION. |
| | JIM WITMER |
| | BUILDING PLAN REVIEW |
| | TEL: (561)805-6715 |
| | FAX: (561)659-8026 |