| 2004-03-09 00:00:00 | BEFORE A PERMIT TO CONSTRUCT MAY BE |
| | ISSUED IMPACT FEES MUST BE PAID TO PALM |
| | BEACH COUNTY, THE PERMIT PLANS STAMPED |
| | BY THAT OFFICE AND A COPY OF THE PAID |
| | RECEIPT ATTACHED TO THE PERMIT |
| | APPLICATION.CALL 561-233-5025 FOR |
| | MORE INFORMATION. |
| | |
| | THE K.D. WINDOWS MULLION NOTICE OF |
| | ACCEPTANCE IS NOT LISTED WITH THE STATE. |
| | |
| | PLEASE SELECT AND MARK THE COMPONENTS |
| | THAT WILL USED IN THE NOTICE OF |
| | ACCEPTANCE REPORTS. |
| | |
| | SHOW A BRIEF LOT DRAINAGE SCHEME SO THAT |
| | COMPLIANCE WITH FBC 1804.1.7 AS AMENDED |
| | BY THE CITY MAY BE DETERMINED. |
| | |
| | NOTE 5, WOOD TRUSS NOTES DOES SHOW THE |
| | MINIMUM 10# LIVE LOAD FOR ATTICS |
| | WITHOUT STORAGE AS REQUIRED BY FBC |
| | TABLE 1604.1. |
| | |
| | THE COMPONENT AND CLADDING PRESSURES |
| | SHOWN ARE NOT FOR A 5:12 PITCH ROOF. |
| | PLEASE REVISE AS NECESSARY. |
| | |
| | SHOW OR NOTE THE SIZE OF THE ROOF AND |
| | WALL ZONE AREAS TO COORDINATE WITH THE |
| | C&C PRESSURES. |
| | |
| | PLEASE PROVIDE NOTICE OF ACCEPTANCE |
| | REPORTS AND ANY OTHER PERTINENT DATA |
| | FOR THE"FIBER CEMENT EXTERIOR LAP |
| | SIDING" SHOWN IN SECTION ON SHEET A2. |
| | |
| | SHOW THE METHOD OF ATTIC VENTILATION AS |
| | REQUIRED BY FBC 2309.7. |
| | |
| | PLEASE PROVIDE STRUCTURAL CALCULATIONS |
| | DEMONSTRATING THAT THE EDGE DISTANCE OF |
| | THE 5/8" X 7" EXPANSION BOLTS TO BE |
| | USED IN THE SILL PLATE IS SUFFICIENT. |
| | |
| | WILL THE FIBER CEMENT SIDING PROVIDE A |
| | MOISTURE BARRIER IN ACCORDANCE WITH FBC |
| | 2303.3?INCLUDE DOCUMENTATION IF THAT |
| | IS THE CASE. |
| | |
| | WILL THE R19 BATTS SPECIFIED IN SECTION |
| | A FIT IN THE 2X4 STUD SPACE? |
| | |
| | CLEARLY NOTE THE WALL SHEATHING DISTANCE |
| | TO GRADE AS SHOWN IN WALL SECTIONS A,B |
| | AND C IN ACCORDANCE WITH FBC 2304.2.5. |