Plan Review Notes
Plan Review Notes For Permit 04020353
Permit Number 04020353
Review Stop B
Sequence Number 1
Notes
Date Text
2004-03-09 00:00:00BEFORE A PERMIT TO CONSTRUCT MAY BE
 ISSUED IMPACT FEES MUST BE PAID TO PALM
 BEACH COUNTY, THE PERMIT PLANS STAMPED
 BY THAT OFFICE AND A COPY OF THE PAID
 RECEIPT ATTACHED TO THE PERMIT
 APPLICATION.CALL 561-233-5025 FOR
 MORE INFORMATION.
  
 THE K.D. WINDOWS MULLION NOTICE OF
 ACCEPTANCE IS NOT LISTED WITH THE STATE.
  
 PLEASE SELECT AND MARK THE COMPONENTS
 THAT WILL USED IN THE NOTICE OF
 ACCEPTANCE REPORTS.
  
 SHOW A BRIEF LOT DRAINAGE SCHEME SO THAT
 COMPLIANCE WITH FBC 1804.1.7 AS AMENDED
 BY THE CITY MAY BE DETERMINED.
  
 NOTE 5, WOOD TRUSS NOTES DOES SHOW THE
 MINIMUM 10# LIVE LOAD FOR ATTICS
 WITHOUT STORAGE AS REQUIRED BY FBC
 TABLE 1604.1.
  
 THE COMPONENT AND CLADDING PRESSURES
 SHOWN ARE NOT FOR A 5:12 PITCH ROOF.
 PLEASE REVISE AS NECESSARY.
  
 SHOW OR NOTE THE SIZE OF THE ROOF AND
 WALL ZONE AREAS TO COORDINATE WITH THE
 C&C PRESSURES.
  
 PLEASE PROVIDE NOTICE OF ACCEPTANCE
 REPORTS AND ANY OTHER PERTINENT DATA
 FOR THE"FIBER CEMENT EXTERIOR LAP
 SIDING" SHOWN IN SECTION ON SHEET A2.
  
 SHOW THE METHOD OF ATTIC VENTILATION AS
 REQUIRED BY FBC 2309.7.
  
 PLEASE PROVIDE STRUCTURAL CALCULATIONS
 DEMONSTRATING THAT THE EDGE DISTANCE OF
 THE 5/8" X 7" EXPANSION BOLTS TO BE
 USED IN THE SILL PLATE IS SUFFICIENT.
  
 WILL THE FIBER CEMENT SIDING PROVIDE A
 MOISTURE BARRIER IN ACCORDANCE WITH FBC
 2303.3?INCLUDE DOCUMENTATION IF THAT
 IS THE CASE.
  
 WILL THE R19 BATTS SPECIFIED IN SECTION
 A FIT IN THE 2X4 STUD SPACE?
  
 CLEARLY NOTE THE WALL SHEATHING DISTANCE
 TO GRADE AS SHOWN IN WALL SECTIONS A,B
 AND C IN ACCORDANCE WITH FBC 2304.2.5.