| Plan Review Notes For Permit 04020306 |
| Permit Number |
04020306 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-13 00:00:00 | DENIED | | | REFERENCE: FBC-2001 FUEL GAS | | | | | | 1) SUBMIT MANUF. SPEC. SHEETS FOR THE | | | REGULATORS. THEY SHALL BE APPROVED BY | | | A RECOGNIZED TESTING AGENCY. | | | 2) SUBMIT MANUF. SPEC. SHEETS FOR THE | | | PE PIPED USED. APPROVAL BY AN APPROVED | | | TESTING AGENCY REQUIRED. | | | 3) REGULATOR REQUIRED AT FUTURE FIRE | | | LOGS. | | | 4) VALVE REQUIRED UPSTREAM OF REGULATORS | | | FOR SERVICE. | | | 5) REGULATORS SHALL BE ACCESSIBLE PER | | | 410.1. SUBMIT INFO HOW THE REGULATOR | | | UPSTREAM OF THE 1-1/4" PE PIPE WILL BE | | | ACCESSIBLE. REGULATOR SHALL BE PROTECTED | | | AGAINST CORROSION. SUBMIT A DETAIL. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|