Plan Review Notes
Plan Review Notes For Permit 04020284
Permit Number 04020284
Review Stop P
Sequence Number 2
Notes
Date Text
2004-02-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 FLORIDA ADMIN. CODE
 FLORIDA STATUTES
  
 1) SUBMIT CALCULATIONS FOR MINIMUM FIX-
 TURES PER TABLE 403.1
 2) SUBMIT DETAILS FOR TOILET ROOM PER
 SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND
 ALL SUBSECTIONS.
 3) SUBMIT DETAIL FOR DRINKING FOUNTAIN
 PER 11-4.15 AND ALL SUBSECTIONS.
 4) SUBMIT CALCULATIONS FOR ROOF DRAINS
 PER SECTION 1106 AND ALL SUBSECTIONS.
 SHOW SIZE OF GUTTER PER TABLE 1106.6.
 SHOW SLOPE OF GUTTER AND SHOW HIGH POINT
 OF GUTTER. SHOW LOCATION AND SIZE OF ALL
 DOWNSPOUTS.
 5) SANITARY AND WATER RISER DIAGRAM ARE
 REQUIRED PER SECTION 104.3.1.1
 6) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE OF THE BLDG.
 7) PER 616G1-16.004 FIRM ADDRESS, FIRM
 LICENSE NUMBER REQUIRED. FS 481.2055.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]