| Plan Review Notes For Permit 04020284 |
| Permit Number |
04020284 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-02-17 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMIN. CODE | | | FLORIDA STATUTES | | | | | | 1) SUBMIT CALCULATIONS FOR MINIMUM FIX- | | | TURES PER TABLE 403.1 | | | 2) SUBMIT DETAILS FOR TOILET ROOM PER | | | SECTIONS 11-4.16, 11-4.19, & 11-4.22 AND | | | ALL SUBSECTIONS. | | | 3) SUBMIT DETAIL FOR DRINKING FOUNTAIN | | | PER 11-4.15 AND ALL SUBSECTIONS. | | | 4) SUBMIT CALCULATIONS FOR ROOF DRAINS | | | PER SECTION 1106 AND ALL SUBSECTIONS. | | | SHOW SIZE OF GUTTER PER TABLE 1106.6. | | | SHOW SLOPE OF GUTTER AND SHOW HIGH POINT | | | OF GUTTER. SHOW LOCATION AND SIZE OF ALL | | | DOWNSPOUTS. | | | 5) SANITARY AND WATER RISER DIAGRAM ARE | | | REQUIRED PER SECTION 104.3.1.1 | | | 6) AN RPZ BACKFLOW IS REQUIRED ON THE | | | WATER SERVICE OF THE BLDG. | | | 7) PER 616G1-16.004 FIRM ADDRESS, FIRM | | | LICENSE NUMBER REQUIRED. FS 481.2055. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|