Plan Review Notes
Plan Review Notes For Permit 04020284
Permit Number 04020284
Review Stop P
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00DENIED
 REFERENCE: FBC-2001 PLUMBING
 FBC-2001 CHAPTER 1
 FBC-2001 CHAPTER 11
 CITY WPB CODE
  
 1) SHT A-1 TOILET ROOMS SHALL BE ACCESS-
 IBLE. SUBMIT DETAILS TO SHOW COMPLIANCE
 WITH SECTIONS 11-4.16, 11-4.19, AND
 11-4.22 AND ALL SUBSECTIONS.
 2) SHT A-1 DRINKING FOUNTAIN SHALL BE
 COMPLIANT WITH 11-4.15 AND ALL SUBSECT-
 IONS. SUBMIT DETAIL.
 3) SHT A-1 INDICATE THE USE OF THE
 SEPTIC TANKS. OUTFALL FROM SEPTIC TANKS
 SHALL DRAIN TO SANITARY SEWER SYSTEM,
 NOT STORMWATER RETENTION AREA.
 4) CONTACT RODNEY COMPO, ENVIRONMENTAL
 COMPLIANCE FOR SIZING OF TANKS. WASTE
 ORD.2938-96. (561) 837-4074
 5) SUBMIT MANUF. SPECIFICATION SHEETS
 TO DETERMINE TYPE OF BACKFLOW DEVICE TO
 BE USED FOR FUTURE EQUIPMENT TO PREVENT
 CROSS CONNECTION. SECTION 608.13
 6) SUBMIT CALCULATIONS FOR ROOF DRAINAGE
 PER SECTION 1106 AND ALL SUBSECTIONS.
 INDICATE GUTTER SIZE, & SLOPE. SHOW THE
 HIGH POINT OF EACH GUTTER. TABLE 1106.6
 SHOW LOCATION AND SIZE OF ALL DOWNSPOUTS
 SIZE PER TABLE 1106.2
 7) ONLY THE FIXTURES WITHIN THE BATH-
 ROOM GROUP SHALL CONNECT TO THE WET-
 VENTED HORIZONTAL BRANCH DRAIN. ANY
 ADDITIONAL FIXTURES SHALL DISCHARGE
 DOWNSTREAM OF THE WET VENT. JANITOR SINK
 SHALL DISCHARGE DOWN STREAM OF ALL
 TOILET ROOM FIXTURES. (SEE SANITARY RIS-
 ER DIAGRAM AND FLOOR PLAN). SEC 909.1
 8) SHT P-1 SANITARY RISER DIAGRAM, THE
 LAVS ARE NOT VENTED. VENT REQUIRED AT
 LAVS PER SECTION 901.2.1
 9) SHT P-1 WATER RISER DIAGRAM, SHUT-OFF
 VALVES REQUIRED AT EACH HOSE BIBB PER
 SECTION 606.2(2).
 10) PER 61G1-16.004 FIRM ADDRESS, FIRM
 LICENSE NUMBER. FS 481.2055
 11) AN RPZ BACKFLOW IS REQUIRED ON THE
 WATER SERVICE.
  
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 653-2692
 E-MAIL [email protected]