| 2004-02-17 00:00:00 | DENIED |
| | REFERENCE: FBC-2001 PLUMBING |
| | FBC-2001 CHAPTER 1 |
| | FBC-2001 CHAPTER 11 |
| | CITY WPB CODE |
| | |
| | 1) SHT A-1 TOILET ROOMS SHALL BE ACCESS- |
| | IBLE. SUBMIT DETAILS TO SHOW COMPLIANCE |
| | WITH SECTIONS 11-4.16, 11-4.19, AND |
| | 11-4.22 AND ALL SUBSECTIONS. |
| | 2) SHT A-1 DRINKING FOUNTAIN SHALL BE |
| | COMPLIANT WITH 11-4.15 AND ALL SUBSECT- |
| | IONS. SUBMIT DETAIL. |
| | 3) SHT A-1 INDICATE THE USE OF THE |
| | SEPTIC TANKS. OUTFALL FROM SEPTIC TANKS |
| | SHALL DRAIN TO SANITARY SEWER SYSTEM, |
| | NOT STORMWATER RETENTION AREA. |
| | 4) CONTACT RODNEY COMPO, ENVIRONMENTAL |
| | COMPLIANCE FOR SIZING OF TANKS. WASTE |
| | ORD.2938-96. (561) 837-4074 |
| | 5) SUBMIT MANUF. SPECIFICATION SHEETS |
| | TO DETERMINE TYPE OF BACKFLOW DEVICE TO |
| | BE USED FOR FUTURE EQUIPMENT TO PREVENT |
| | CROSS CONNECTION. SECTION 608.13 |
| | 6) SUBMIT CALCULATIONS FOR ROOF DRAINAGE |
| | PER SECTION 1106 AND ALL SUBSECTIONS. |
| | INDICATE GUTTER SIZE, & SLOPE. SHOW THE |
| | HIGH POINT OF EACH GUTTER. TABLE 1106.6 |
| | SHOW LOCATION AND SIZE OF ALL DOWNSPOUTS |
| | SIZE PER TABLE 1106.2 |
| | 7) ONLY THE FIXTURES WITHIN THE BATH- |
| | ROOM GROUP SHALL CONNECT TO THE WET- |
| | VENTED HORIZONTAL BRANCH DRAIN. ANY |
| | ADDITIONAL FIXTURES SHALL DISCHARGE |
| | DOWNSTREAM OF THE WET VENT. JANITOR SINK |
| | SHALL DISCHARGE DOWN STREAM OF ALL |
| | TOILET ROOM FIXTURES. (SEE SANITARY RIS- |
| | ER DIAGRAM AND FLOOR PLAN). SEC 909.1 |
| | 8) SHT P-1 SANITARY RISER DIAGRAM, THE |
| | LAVS ARE NOT VENTED. VENT REQUIRED AT |
| | LAVS PER SECTION 901.2.1 |
| | 9) SHT P-1 WATER RISER DIAGRAM, SHUT-OFF |
| | VALVES REQUIRED AT EACH HOSE BIBB PER |
| | SECTION 606.2(2). |
| | 10) PER 61G1-16.004 FIRM ADDRESS, FIRM |
| | LICENSE NUMBER. FS 481.2055 |
| | 11) AN RPZ BACKFLOW IS REQUIRED ON THE |
| | WATER SERVICE. |
| | |
| | |