2004-03-04 00:00:00BUILDING PLAN REVIEW
 PERMIT: 04020252
 ADD: 5325 GREENWOOD AV
 CONT: ANDERSON-MOORE
 TEL: (561)635-6935NAT HEALY
 FL BLD CODE= 2001 FLORIDA BUILDING CODE
  
 1ST REVIEW
 ACTION: DENIED
  
 1) PLANS, SPECIFICATIONS,REPORTS OR
 OTHER DOCUMENTS PREPARED BY THE DESIGN
 PROFESSIONAL AND BEING FILED FOR PUBLIC
 RECORD SHALL HAVE THE SIGNATURE AND
 SEAL OF THE DESIGN PROFESSIONAL AFFIXED
 TO THE DOCUMENT.
 FL STATE STAT: 61G15-23.002 ENGINEERS
 FL ATATE STAT: 61G16.003 ARCHITECTS
  
 MISING SEAL ON SHEET A.1
  
 2) SHEET T.1 CODE NOTES, WRONG ACCESSIBI
 LITY CODE SHOULD READ: 2001 FLORIDA CODE
 CHAP 11 ACCESSIBILITY
  
 3)11-4.1.6(2) DUTY TO PROVIDE AN
 ACCESSIBLE PATH OF TRAVEL TO ALTERED
 AREAS SHALL BE DEEMED DISPROPORTIONATE
 TO THE OVERALL ALTERATION WHEN THE COST
 EXCEEDS 20 % OF THE COST OF THE ALTERA-
 TION TO THE PRIMARY FUNCTION AREA.
 (A)(I) AN ACCESSIBLE ENTRANCE
 (II) AN ACCESSIBLE ROUTE
 (III) AT LEAST ONE ACCESSIBLE REST-
 ROOM FOR EACH SEX OR A SINGLE
 UNISEX RESTROOM
 (IIII) ACCESSIBLE TELEPHONE
 (IV) ELEMENTS SUCH AS PARKING, STOR-
 AGE OR ALARMS.
  
 SEE SHEET A.1 OF UNSEALED PLAN, 2 DOORS
 THAT DO NOT MEET CLEARENCES AT DOORS
 SEE 11-4.13.6
  
 4) FOR THE FIRE RATED PARTITION:
 704.2.1.4 CORRIDOR PARTITIONS, SMOKE
 STOP PARTITIONS, HORIZONTAL EXIT PART-
 ITIONS, EXIT ENCLOSURES, AND FIRE
 RATED WALLS REQUIRED TO HAVE PROTECTED
 OPENINGS SHALL BE EFFECTIVELY AND
 PERMANETLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE
 AUTHORITY HAVING JURISDICTION. SUCH IDEN
 TIFICATION SHALL BE ABOVE ANY DECORATIVE
 CEILING CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING" FIRE & SMOKE BARRIER
 PROTECT ALL OPENINGS".
  
 BUILDING PLAN REVIEW
 JIM WITMER
 TEL: (561)805-6715
 FAX: (561)659-8026