Plan Review Notes
Plan Review Notes For Permit 04020179
Permit Number 04020179
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00**************** UNSAT ***************
  
 1)NOTE: PLEASE SEE 210.52E FOR MISSING
 FRONT GFI RECEPT.
  
 2)NOTE: PLEASE SEE RECEPT IN MASTER
 BATH TO BE W/IN 3' FROM LAV. 210.52D
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR BETWEEN MAIN AND
 PANEL. PER 250.24, SIZE PER 250.122
  
 4)NOTE: PLEASE SEE MISSING LT FIXTURE
 IN HALL OUTSIDE LAUNDRY ROOM. REQ'D
 PER 210.70 LS 101 5-8.
  
 5)NOTE: PLEASE SEE PLANS ARE MISSING ALL
 SERVICE EQUIPMENT. METER/ MAIN/ PANEL
 NOT SHOWN.
  
 6)NOTE: PLAN INDICATE POOL PUMP YET,
 PANEL SCHEDULE DOES NOT LIST POOL
 EQUIPMENT?
  
 7)NOTE: PLEASE HAVE PLANS SIGNED BY THE
 ARCH OF RECORD. SIGNATURE ON PLANS DO
 NOT CORRELATE WITH SIGNATURE ON FILE FOR
 ARCH. PER FS 481.221
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  