Plan Review Notes
Plan Review Notes For Permit 04020164
Permit Number 04020164
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-09 00:00:00********** UNSAT *************
  
 1)NOTE: PLEASE SEE PANEL SCHEDULE FOR
 PANEL "A". SHOWN AS 60A, YET MDP SHOWS
 70A OCP> WITH #6 AWG.
 PLEASE CORRELATE.
  
 2)NOTE: PLEASE SEE "TYPICAL NOTE" ON
 RISER POINTING AT MDP1 ON FIRST FLR
 INSTEAD OF APT PANEL. (MISPRINT)
  
 3)NOTE: PLEASE SIGN PLANS WITH A
 COMPLETE SIGNATURE AS SHOWN ON LICENSE.
 (FIRST AND LAST NAME) MIN PER FBPE'S.
 PLEASE ALSO INCLUDE ENGINEER'S NAME ON
 ON TITLE BLOCK AS REQ'D UNDER
 FAC 61G15-23.002.
 HOW LICENSE IS SIGNED ON LICENSE W/
 STATE IS HOW LICENSE MUST BE SIGNED AND
 DATED. THIS HAS COME UP DUE TO A
 SEPARATE CASE W/ FBPE'S.
 IF THERE ARE ANY QUESTIONS WITH THIS
 COMMENT, PLEASE CALL.
  
 4)NOTE: PLEASE PROVIDE INFORMATION ON
 WEATHER OR NOT BLDG CONATINS AN ELEVATOR
 PLEASE LIST/ SHOW DEVICE HEIGHTS PER
 FHAR, 24 CFR 100.205. REQ'D FOR FIRST
 FLR AND ALSO REQ'D FOR 2ND AND 3RD IF
 VERTICAL ACCESSABILITY IS PROVIDED.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]