| Plan Review Notes For Permit 04020114 |
| Permit Number |
04020114 |
|
| Review Stop |
P |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-08-11 00:00:00 | DENIED | | | REFERENCE: FBC-2001 PLUMBING | | | FBC-2001 CHAPTER 1 | | | FBC-2001 CHAPTER 11 | | | FLORIDA ADMINISTRATIVE CODE | | | FLORIDA STATUTES | | | | | | FROM PREVIOUS REVIEW: | | | 1) DUE TO CHANGE OF OCCUPANCY THE TOILET | | | ROOM SHALL HAVE TO COMPLY WITH 11-4.22, | | | 11-4.16, 11-4.19 AND ALL SUBSECTIONS. | | | - PLEASE SUBMIT A DETAIL SHOWING COMPLI- | | | ANCE. | | | FROM PREVIOUS REVIEW: | | | 2) PER COMMENT RESPONSE FOR A GREASE IN- | | | TERCEPTOR, A SAMPLE POINT SHALL BE RE- | | | QUIRED ON SANITARY LINE FROM DELI AREA | | | AND UPSTREAM OF THE TOILET ROOM. PLEASE | | | SHOW ON PLANS AND ON SANT. RISER DIAGRAM | | | SECTION 104.2.1. - THE SANT. IS SHOWN AS | | | DRAINING THE OPPOSITE DIRECTION, AND IF | | | THIS IS THE CASE, THE TOILET ROOM SHALL | | | CONNECT DOWNSTREAM OF THE HAND SINK WITH | | | THE SAMPLE POINT UPSTREAM OF THAT CONN- | | | ECTION. SOIL SYSTEM SHALL NOT DRAIN THRU | | | THE SAMPLE POINT. | | | FROM PREVIOUS REVIEW: | | | 5) INFORMATION MISSING ON THE TITLE | | | BLOCK REQUIRED FOR FAC 61G1-16.004(6), A | | | SPACE FOR PRINTED NAME OF THE PERSON | | | SEALING THE DOCUMENT. FS 481.2055. | | | FROM PREVIOUS REVIEW: | | | 6) THE ORIGINAL PERMIT APPLICATION IS | | | REQUIRED FOR PERMIT. | | | NEW COMMENT: | | | 1B) MOP SINK SHALL BE VENTED. SEE RED | | | LINE CORRECTION OF RISER DIAGRAM FOR | | | EXAMPLE. | | | | | | REVIEW BY KEN STEVENS | | | (561) 805-6721 | | | FAX (561) 653-2692 | | | E-MAIL [email protected] |
|