| 2004-07-14 00:00:00 | *************** UNSAT ************** |
| | |
| | PLEASE SEE THAT PLANS SUBMITTED |
| | FOR ELECTRICAL REVIEW ARE NOT THE SAME |
| | AS SUBMITTED UNDER A SEPARATE ELECTRICAL |
| | PERMIT. # 04050876 |
| | PLEASE SEE THAT DUE TO CHANGE IN OCCU- |
| | -PANCY ALL ELETCRICAL WORK AND PLANS |
| | MUST BE BROUGHT UP TO CODE FOR COMM |
| | MERCHANTILE OCCUPIED BLDG. |
| | PLANS SUBMITTED UNDER SEPARATE PERMIT |
| | DID NOT MEET COMPLETE CODE COMPLIANCE |
| | FOR ITS INTENT AND USE. |
| | |
| | 1)NOTE: PLEASE SEE 600.5 FOR MISSING |
| | REQUIRED SIGN CIRCUIT. |
| | |
| | 2)NOTE: PLEASE SEE 210.62 FOR MIN REQ- |
| | -UIRED SHOW WINDOW RECEPTS. |
| | |
| | 3)NOTE: PLEASE SEE 700.12E FOR CIRCUIT- |
| | -ING OF EM/EXT LTS. |
| | |
| | 4)NOTE: PLEASE SEE SEC'S/ FEEDERS ARE |
| | NOT LARGE ENOUGH FOR SERVICE SIZE SHOWN. |
| | PLEASE SEE 310.16. |
| | |
| | 5 )NOTE: PLEASE SHOW LOAD CALCULATIONS, |
| | PLEASE SHOW PER |
| | 220.3,220.10,220.11,220.13 ETC. |
| | PLEASE ALSO SHOW ALL CONTINOUS LOADS |
| | AT 125% PER 215.3,230.42 |
| | |
| | 6)NOTE: PLEASE SEE THAT RAISED SEAL FOR |
| | ARCHITECT MUST BE CLEAR AND VISABLE WITH |
| | ALL INFORMATION ON SAID SEAL. |
| | FS 481.221 |
| | |
| | 7)NOTE: PLEASE SEE 210.8B3 FOR MIN |
| | GFI RECEPTS TO MEET CODE COMPLIANCE FOR |
| | KITCHEN AREA. |
| | |
| | 8)NOTE: PLEASE SEE 3-PHASE BREAKERS |
| | SHOWN ON PANEL SCHEDULE YET, SERVICE IS |
| | SHOWN AS 1-PHASE? ALONG W/ LOAD DETAIL? |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |