| Plan Review Notes For Permit 04020100 |
| Permit Number |
04020100 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-03-03 00:00:00 | BUILDING PLAN REVIEW | | | PERMIT: 04020100 | | | ADD: 401 N DIXIE HWY | | | CONT: M. A. C. CONSTRUCTION | | | TEL: (786)357-0214 | | | FL BLD CODE= 2001 FLORIDA BUILDING CODE | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) TABLE 803.3 MINIMUM INTERIOR FINISH | | | CLASSIFICATION; PROVIDE INFORMATION | | | BASED ON INTERIOR FINISH REQUIREMENTS | | | BASED ON OCCUPANCY: BUSINESS. | | | | | | 2)11-4.13.6 MANEUVERING CLEARENCES | | | AT DOORS. MINIMUM MANEUVERING CLEARENCES | | | AT DOORS THAT ARE NOT AUTOMATIC OR | | | POWER-ASSISTED SHALL BE AS SHOWN IN | | | FIG. 25. THE FLOOR OR GROUND AREA WITH | | | IN THE REQUIRED CLEARENCES SHALL BE | | | CLEAR & LEVEL. | | | THE 2 END OFFICES ON THE RIGHT SIDE OF | | | THE SHEET DO NOT HAVE 12" CLEAR ON THE | | | LATCH SIDE OF THE DOOR. | | | | | | 3) PLANS INDICATE THE LOCKS OR LATCHSETS | | | ARE TO MATCH EXISTING. PLANS DO NOT | | | INDICATE COMPLIANCE WITH 11-4.13.9 | | | ACCESSIBLE DOORS: LEVER-OPERATED MECHAN- | | | ISMS, PUSH-TYPE MECHANISMS, AND U SHAPED | | | HANDLES ARE ACCESSIBLE DESIGNS. | | | | | | 4) PLANS INDICATE WORK ON THE 5TH FLOOR | | | THE PERMIT APP DOES NOT INDICATE THIS | | | SO SAID WORK HAS BEEN STRUCK FROM PERMIT | | | BUILDING PLAN REVIEW | | | JIM WITMER | | | TEL: (561)805-6715 | | | FAX: (561)659-8026 |
|