| Plan Review Notes For Permit 04020058 |
| Permit Number |
04020058 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-06-17 00:00:00 | ************** UNSAT ********** | | | | | | 1)NOTE: PLEASE SEE ATTACHED SHEET FROM | | | STATE DBPR SHOWING LICENSE FOR ARCHITECT | | | AS DELINQUENT AND FIRM AS ALSO BEING | | | DELINQUENT.FS 481.219/FAC 61G1-16.004 | | | PLEASE INCLUDE ALL LICENSE #'S ON TITLE | | | BLOCK AS REQUIRED PER ABOVE. | | | | | | 2)NOTE: PLEASE SEE PLANS ARE NOW SHOWING | | | MORE WORK FOR ENTIRE UNIT, HOWEVER PANEL | | | SCHEDULES AND LOAD CALCULATIONS HAVE | | | NOW BEEN REMOVED? | | | PLEASE COMPLETE LOAD CALCS AND PANELS | | | TO CORRELATE WITH PLANS. | | | | | | 3)NOTE: PLEASE SEE NOTES FOR REQUIRED | | | ARC FAULT PROTECTION HAS NOW BEEN | | | REMOVED. 2002 NEC 210.12 | | | | | | 4)NOTE: PLANS ALSO MENTIONS " NO ELEC- | | | -TRICAL REVISIONS IN THIS AREA" HOWEVER | | | PLANS SHOW ELECTRICAL WORK?? | | | | | | PLANS/INSPECTIONS HAVE NOW BEEN PLACED | | | ON HOLD. | | | | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|