| 2004-06-29 00:00:00 | ****CORRECTIONS**** |
| | |
| | SAMANTHA HILL, BUILDING PLANS EXAMINER |
| | [email protected] |
| | |
| | 1.)SEPARATE PERMITS REQUIRED. |
| | |
| | 2.)HISTORIC APPROVAL REQUIRED.PLEASE |
| | HAVE THE PLANS STAMPED BY HISTORIC. |
| | |
| | 3.)SEE THE PREVIOUS LISTS.HOW WILL |
| | THE HANDRAIL BE FASTENED TO COMPLY |
| | WITH FBC1608.2?IN OTHER WORDS, HOW |
| | WILL YOU ATTACH THIS TO THE WALL?THIS |
| | CORRECTION HAS BEEN ON EACH LIST; PLEASE |
| | HAVE THE ENGINEER CALL ME IF HE DOESN'T |
| | UNDERSTAND THE CORRECTION. |
| | |
| | 4.)CONNECTOR MTS37 ISN'T IN THE |
| | CATALOG.YOU GAVE A SPEC SHEET FOR |
| | MST37.FASTENING STILL CONFLICTS. |
| | PLEASE SEE ATTACHED.FASTENING FOR SP5 |
| | ALSO CONFLICTS (SEE ATTACHED).CHECK |
| | ALL CONNECTORS.PLEASE HAVE THE |
| | ENGINEER CONTACT ME IF HE DOES NOT |
| | UNDERSTAND THIS CORRECTION AS IT HAS |
| | BEEN MADE 3 TIMES WITHOUT BEING PROPERLY |
| | CORRECTED. |
| | |
| | 5.)ALL OF THE OTHER PLANS SUBMITTED |
| | REFERRED TO FBC2001.NOW THE PLANS |
| | HAVE BEEN CHANGED TO FBC2002.THE |
| | GOVERNING CODE IS STILL FBC2001, PLEASE |
| | CORRECT. |
| | |
| | 6.)A 4X FEE HAS BEEN CHARGED PER |
| | FS553.80(2)(B). |