| Plan Review Notes For Permit 04020057 |
| Permit Number |
04020057 |
|
| Review Stop |
E |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2004-05-14 00:00:00 | *********** UNSAT *********** | | | | | | 1)NOTE: PLEASE SEE PLANS STILL HAVE | | | PLACES WHERE 1999 NEC IS REFERENCED? | | | | | | 2)NOTE: PLEASE SEE FAC 61G15-23.002 | | | PLEASE INCLUDE ALL INFORMATION ON TITLE | | | BLOCK FOR ENGINEER. THIS IS REQ'D TO BE | | | PRINTED ON PLANS. PLEASE ALSO SEE FS | | | 471.025, A SIGNATURE IS REQ'D, PER | | | FS AND FBPE'S INITIALS ARE NOT PERMITTED | | | PLEASE NOTE: THIS IS TO PROTECT THE | | | ENGINEER/ FIRMS. | | | SIGNATURE INFORMATION HAS BEEN GONE OVER | | | W/ MR BUCK AND HE IS NOW AWARE OF WHAT | | | NEEDS TO BE DONE FOR THIS. | | | | | | 3)NOTE: PLEASE SEE RISER, AN EQUIPMENT | | | GROUND NOTE SHOWS AN EQUIP GRND FROM | | | TO METER, AND FROM METER TO MAIN ALSO. | | | PLEASE SEE 250.6,250.24, AN EQUIP GRND | | | IS ONLY INSTALLED "AFTER THE FIRST MEANS | | | OF DISC". PLEASE ADJUST RISER. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|