| Plan Review Notes For Permit 04020057 |
| Permit Number |
04020057 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-13 00:00:00 | DENIED; | | | 1.AUTOMATIC CLOTHES WASHER REQUIRED. SEE | | | FBC PLUMBING TABLE 403.2 ONE AND TWO | | | FAMILY DWELLINGS. | | | 2.SANITARY RISER DIAGRAM NOT TO CODE. | | | KITCHEN SINK IS NOT VENTED, BATHROOM | | | CANNOT BE INSTALLED AS DRAWN. | | | 3.IS W/H 30 OR 50 GAL.? | | | 4.H2O RISER DIAGRAM, SHOCK ARRESTORS NOT | | | AIR CHAMBERSARE REQUIRED PER SEC 604.9 | | | 5.PLUMBING NOTE #1. BUILDING SEWER IS | | | REQUIRED TO BE INSTALLED TO THE PUBLIC | | | SEWER SYSTEM. SEPIC TANK NEEDS TO BE | | | REMOVED. | | | 6.NOTE # 10 REMOVE NOTE HOT WATER SHOULD | | | 120 DEG. ONLY COMMERCIAL DISHWASHER | | | REQUIRE 180 DEG. WATER. | | | PLUMBING PLAN REVIEW BY; | | | JOHN LEECH | | | 805-6695 |
|