| Date |
Text |
| 2004-02-13 00:00:00 | ******************* UNSAT ************* |
| | |
| | 1)NOTE: PLEASE SEE FAC 61G15-23.002 FOR |
| | ALL INFORMATION REQ'D ON A TITLE BLOCK. |
| | PLANS DO NOT CONTAIN TITLE BLOCK. |
| | PLEASE ALSO SEE FS 471 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 SHOWN FOR PANEL,NOT MAIN |
| | |
| | 3)NOTE: PLEASE SEE A-4, REFERENCES 1999 |
| | NEC. WE ARE UNDER THE 2002. |
| | |
| | 4)NOTE: MISSING EQUIPMENT GROUNDING |
| | CONDUCTOR FROM MAIN TO PANEL. 250.110, |
| | 250.24, SIZE PER 250.122 |
| | |
| | 5)NOTE: PLEASE SEE NOTE ON RISER MENTION |
| | -S WEATHERHEAD TO BE 3' ABOVE ROOF. |
| | PLEASE SEE THAT THIS MAY CHANGE DUE TO |
| | ACTUAL LOCATION AND CIRCUMSTANCES OF |
| | ROOF. FYI. |
| | |
| | 6 )NOTE: PLEASE LIST THE REQ'D ARC |
| | FAULT PROTECTED CURCUIT(S) ON PANEL |
| | SCHEDULE. PLEASE SEE THAT ALL "OUTLETS" |
| | IN BEDROOMS ARE TO BE PROTECTED , |
| | INCLUDING, LTS, RECEPTS, SD'S ETC. |
| | |
| | 7 )NOTE: PLEASE SEE MISSING REQ'D EGRESS |
| | LIGHTING AND/OR CLARIFY EGRESS LIGHTING |
| | PER 210.70 AND LS-101 5-8 |
| | MISSING AR FRONT DOOR. |
| | |
| | 8)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | 20' FROM COOKING APPL. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | "PLEASE MOVE FIRST FLR CLOSER TO STAIRS" |
| | |
| | 9)NOTE: PLEASE SHOW ANY LV/ TV/ PHONE |
| | ON PLANS AT THIS TIME, OR PLANS WILL BE |
| | REQ'D TO BE SUBMITTED AT TIME OF APPLI- |
| | -CATION. THIS IS ONLY A NOTE AND IS NOT |
| | REQ'D. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |
| | DEWEY PALMER |
| | ELECTRICAL PLAN REVIEW |
| | CITY OF WEST PALM BEACH |
| | CONSTUCTION SERVICES DEPT. |
| | 561-805-6717 |
| | [email protected] |