Plan Review Notes
Plan Review Notes For Permit 04020025
Permit Number 04020025
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00*************** UNSAT ***********
  
 1)NOTE: PLEASE HAVE PLANS SIGNED,DATED
 AND SALED BY THE ARCH OF RECORD.
 SIGNATURE DOES NOT COORALET WITH
 SIGNATURE ON FILE.
 PER FS 481.221
  
 2)NOTE: SD MISSING OUTSIDE BEDROOM #3
 NFPA-72 8-1.4.1.6.2
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL
 PER 250.110,250.24 SIZE PER 250.122
  
 4)NOTE: PLEASE SEE GFI TO BE W/IN 3'
 FROM LAV IN MASTER AND BATH #2.
 210.52
  
 5)NOTE: PLEASE SEE PLANS DO NOT SHOW
 MAIN NEXT TO METER? PLEASE CORRELATE
 WITH RISER.
  
 6)NOTE: PLEASE SEE MISSING RECEPT IN
 WHAT APPEARS TO BE A BEDROOM #4. 210.52
 2' OF WALL.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  