| Plan Review Notes For Permit 04020025 |
| Permit Number |
04020025 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-17 00:00:00 | *************** UNSAT *********** | | | | | | 1)NOTE: PLEASE HAVE PLANS SIGNED,DATED | | | AND SALED BY THE ARCH OF RECORD. | | | SIGNATURE DOES NOT COORALET WITH | | | SIGNATURE ON FILE. | | | PER FS 481.221 | | | | | | 2)NOTE: SD MISSING OUTSIDE BEDROOM #3 | | | NFPA-72 8-1.4.1.6.2 | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL | | | PER 250.110,250.24 SIZE PER 250.122 | | | | | | 4)NOTE: PLEASE SEE GFI TO BE W/IN 3' | | | FROM LAV IN MASTER AND BATH #2. | | | 210.52 | | | | | | 5)NOTE: PLEASE SEE PLANS DO NOT SHOW | | | MAIN NEXT TO METER? PLEASE CORRELATE | | | WITH RISER. | | | | | | 6)NOTE: PLEASE SEE MISSING RECEPT IN | | | WHAT APPEARS TO BE A BEDROOM #4. 210.52 | | | 2' OF WALL. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|