Plan Review Notes
Plan Review Notes For Permit 04020023
Permit Number 04020023
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00**************** UNSAT *****************
  
 1)NOTE: PLEASE HAVE PLANS SIGNED WITH
 SIGNATURE FROM ARCH OF RECORD PER FS
 481.221.
 SIGNATURE DOES NOT MATCH WITH SIGNATURE
 ON FILE FOR ARCH.
  
 2)NOTE: PLEASE SEE MISSING SD OUTSIDE
 BEDROOM #3. NFPA-72 8-1.4.1.6.2
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 PER 250.110,250.24, SIZE PER 250.122
  
 4)NOTE: PLEASE SEE RECEPT SPACING TO BE
 3' MAX FROM SINKS. 210.52D. MASTER BATH
 AND BATH#2.
  
 5)NOTE: PLANS DO NOT INDICATE MAIN AS
 SHOWN ON RISER DIAGRAM. PLEASE CORRELATE
  
 6)NOTE: PLEASE SEE MISSING RECEPT PER
 210.52, 2' OF WALL SPACE IN WHAT APPEARS
 TO BE A BEDROOM #4.?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.