| Plan Review Notes For Permit 04020023 |
| Permit Number |
04020023 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2004-02-17 00:00:00 | **************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE HAVE PLANS SIGNED WITH | | | SIGNATURE FROM ARCH OF RECORD PER FS | | | 481.221. | | | SIGNATURE DOES NOT MATCH WITH SIGNATURE | | | ON FILE FOR ARCH. | | | | | | 2)NOTE: PLEASE SEE MISSING SD OUTSIDE | | | BEDROOM #3. NFPA-72 8-1.4.1.6.2 | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | PER 250.110,250.24, SIZE PER 250.122 | | | | | | 4)NOTE: PLEASE SEE RECEPT SPACING TO BE | | | 3' MAX FROM SINKS. 210.52D. MASTER BATH | | | AND BATH#2. | | | | | | 5)NOTE: PLANS DO NOT INDICATE MAIN AS | | | SHOWN ON RISER DIAGRAM. PLEASE CORRELATE | | | | | | 6)NOTE: PLEASE SEE MISSING RECEPT PER | | | 210.52, 2' OF WALL SPACE IN WHAT APPEARS | | | TO BE A BEDROOM #4.? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|