Plan Review Notes
Plan Review Notes For Permit 04020021
Permit Number 04020021
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00*************** UNSAT *****************
  
 1)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL.
 PER 250.24, SIZE OER 250.122
  
 2)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL IN WHAT APPEARS TO BE A BED-
 -ROOM #4. 210.52
  
 3)NOTE: PLEASE SEE 210.52D FOR REQ'D
 SPACING OF RECEPTS IN BATHS. RECEPT TO
 BE A MAX OF 3' FROM EDGE OF LAV.
 MASTER BATH ABD BATH#2.
  
 4)NOTE: PLEASE SEE PLANS DO INDICATE
 A MAIN NEXT TO METER AS SHOWN ON RISER
 DIAGRAM. PLEASE CORRELATE.
  
 5)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2
 MISSING SD OUTSIDE BEDRROM #3.
  
 6)NOTE: PLEASE HAVE PLANS SIGNED BY THE
 ARCH OF RECORD. SIGNATURE ON PLANS DO
 NOT CORRELATE WITH SIGNATURE ON FILE.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 CITY OF WEST PALM BEACH
 CONSTUCTION SERVICES DEPT.
 561-805-6717
 [email protected]