| 2004-02-17 00:00:00 | *************** UNSAT ***************** | | | | | | 1)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL. | | | PER 250.24, SIZE OER 250.122 | | | | | | 2)NOTE: PLEASE SEE MISSING RECEPT FOR | | | 2' OF WALL IN WHAT APPEARS TO BE A BED- | | | -ROOM #4. 210.52 | | | | | | 3)NOTE: PLEASE SEE 210.52D FOR REQ'D | | | SPACING OF RECEPTS IN BATHS. RECEPT TO | | | BE A MAX OF 3' FROM EDGE OF LAV. | | | MASTER BATH ABD BATH#2. | | | | | | 4)NOTE: PLEASE SEE PLANS DO INDICATE | | | A MAIN NEXT TO METER AS SHOWN ON RISER | | | DIAGRAM. PLEASE CORRELATE. | | | | | | 5)NOTE: PLEASE SEE NFPA-72 8-1.4.1.6.2 | | | MISSING SD OUTSIDE BEDRROM #3. | | | | | | 6)NOTE: PLEASE HAVE PLANS SIGNED BY THE | | | ARCH OF RECORD. SIGNATURE ON PLANS DO | | | NOT CORRELATE WITH SIGNATURE ON FILE. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|