Plan Review Notes
Plan Review Notes For Permit 04020019
Permit Number 04020019
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-17 00:00:00*************** UNSAT *************
  
 1)NOTE: PLEASE SEE MISSING SD OUTSIDE
 BEDROOM #3. NFPA-72 8-1.4.1.6.2
  
 2)NOTE: PLEASE SEE 210.52D. MAX OF 3'
 FROM LAV'S . PLEASE SEE MASTER BATH AND
 BATH #2.
  
 3)NOTE: PLEASE SEE MISSING EQUIPMENT
 GROUNDING CONDUCTOR FROM MAIN TO PANEL
 PER 250.24, SIZE PER 250.122
  
 4)NOTE: PLANS DO NOT SHOW MAIN NEXT
 TO METER? PLEASE CORRELATE WITH RISER
 DIAGRAM.
  
 5)NOTE: PLEASE HAVE PLANS SIGNED BY THE
 ARCH OF RECORD. SIGNATURE DOES NOT MATCH
 WITH SIGNATURE ON FILE.
 MAST BE SIGNED BY THE ARCH.FS 481.221
  
 6)NOTE: PLEASE SEE MISSING RECEPT FOR
 2' OF WALL SPACE IN WHAT APPEARS TO BE
 BEDROOM #4?
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  