| 2004-02-17 00:00:00 | *************** UNSAT ************* | | | | | | 1)NOTE: PLEASE SEE MISSING SD OUTSIDE | | | BEDROOM #3. NFPA-72 8-1.4.1.6.2 | | | | | | 2)NOTE: PLEASE SEE 210.52D. MAX OF 3' | | | FROM LAV'S . PLEASE SEE MASTER BATH AND | | | BATH #2. | | | | | | 3)NOTE: PLEASE SEE MISSING EQUIPMENT | | | GROUNDING CONDUCTOR FROM MAIN TO PANEL | | | PER 250.24, SIZE PER 250.122 | | | | | | 4)NOTE: PLANS DO NOT SHOW MAIN NEXT | | | TO METER? PLEASE CORRELATE WITH RISER | | | DIAGRAM. | | | | | | 5)NOTE: PLEASE HAVE PLANS SIGNED BY THE | | | ARCH OF RECORD. SIGNATURE DOES NOT MATCH | | | WITH SIGNATURE ON FILE. | | | MAST BE SIGNED BY THE ARCH.FS 481.221 | | | | | | 6)NOTE: PLEASE SEE MISSING RECEPT FOR | | | 2' OF WALL SPACE IN WHAT APPEARS TO BE | | | BEDROOM #4? | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|