Plan Review Notes
Plan Review Notes For Permit 04011446
Permit Number 04011446
Review Stop E
Sequence Number 3
Notes
Date Text
2004-06-22 00:00:00********** UNSAT ***********
  
 1)NOTE: PLANS HAVE COME BACK AS A SUBMIT
 -TAL. NO REVISIONS ARE SHOWN. PLEASE
 SEE PREVIOUS COMMENTS ABOUT LOAD CALCS
  
 FEE OWED FOR REVSIONS OR AS RE-STAMP.
  
 2 )NOTE: PLEASE SEE 220.3B4.
 PLEASE SHOW ALL RECESSED LTS BASED ON
 MAX WATTAGE FOR FIXTURE(S). THIS MAY NOT
 BE FIGURED IN W/ 3W/PER SQ FT.
 PLEASE PROVIDE FIXTURE INFORMATION ON
 LEGEND.
  
 3)NOTE: PLEASE SEE PLANS CONTAIN A
 RAISED SEAL OVER COPIED SIGNATURE.
 PLANS MUST CONTAIN ORIGINAL SIGNATURE
 AND RAISED SEAL.PER FS 481.221/ FAC
 61G1-16.004.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  