| 2004-03-19 00:00:00 | BUILDING REVIEW PROVISO: |
| | 1-ATTIC LIVE LOAD IS MEASURED IN PSF NOT |
| | PSI. REVISE NOTE AS REQUIRED. |
| | 2-ENERGY CALCULATIONS: A)REVISE CARDINAL |
| | ORIENTATION TO MATCH PLANS SINCE THEY |
| | WERE NOT CALCULATED FOR WORST CASE |
| | SCENARIO WHEN BUILDING SAME MODEL. |
| | B)REVISE OVERHANG LENGTH AND HEIGHT |
| | SHOWN ON CALCS TO MATCH PLANS. |
| | 3-PROVIDE COMPLETE FLORIDA OR LOCAL |
| | PRODUCT APPROVAL FOR: A)FRENCH DOORS |
| | WITH SIDELITES. SEE PLANS. |
| | B)SINGLE HUNG WINDOWS. IMPACT. |
| | C)ALL STRUCTURAL CONNECTORS. |
| | D)CONNECTORS WITHOUT PRODUCT APPROVAL |
| | STILL REQUIRE ONE. LETTER BY ARCHITECT |
| | ISN'T SUFFICIENT. STILL NEEDS COMPLETE |
| | INFORMATION FOR FLORIDA/LOCAL PRODUCT |
| | APPROVAL. |
| | E)FIXED WINDOW (IMPACT) WITH SIZE AS |
| | SPECIFIED AT KITCHEN AND DINING AREA. |
| | F)NEED FRENCH DOORS WITH SIDELITES AND |
| | TRANSOM ABOVE ASSEMBLY AS SHOWN ON |
| | PLANS. DETAIL SHOWN ON SHEET A6 IS THE |
| | SAME INFO. FROM PRODUCT APPROVAL BUT |
| | IT DOESN'T SPECIFY HOW IS THE ASSEMBLY |
| | PUT TOGETHER. INCLUDINGHEADER SPECS |
| | AND ATTACHMENT TO SIDE COLUMNS, AND |
| | DOORS AND TRANSOM ATTACHMENT TO HEADER |
| | 4-PROVIDE COMPLETE DETAIL FOR STRUCTURAL |
| | FACIA TO SUPPORT TRUSSES AT REAR PORCH |
| | SINCE THERE ISN'T BEAM TO SUPPORT THEM |
| | SEC. 104.2.1.2 CITY AMENDMENTS TO FBC. |
| | 5-SPECIFY CONNECTOR FOR BEAMS RESTING |
| | ON MASONRY WALL AT ENTRY PORCH. SEE |
| | ROOF FRAMING PLAN. SECTION 104.2.1.2 |
| | CITY AMENDMENTS TO FBC 2001. |