Plan Review Notes
Plan Review Notes For Permit 04011446
Permit Number 04011446
Review Stop B
Sequence Number 2
Notes
Date Text
2004-03-19 00:00:00BUILDING REVIEW PROVISO:
 1-ATTIC LIVE LOAD IS MEASURED IN PSF NOT
 PSI. REVISE NOTE AS REQUIRED.
 2-ENERGY CALCULATIONS: A)REVISE CARDINAL
 ORIENTATION TO MATCH PLANS SINCE THEY
 WERE NOT CALCULATED FOR WORST CASE
 SCENARIO WHEN BUILDING SAME MODEL.
 B)REVISE OVERHANG LENGTH AND HEIGHT
 SHOWN ON CALCS TO MATCH PLANS.
 3-PROVIDE COMPLETE FLORIDA OR LOCAL
 PRODUCT APPROVAL FOR: A)FRENCH DOORS
 WITH SIDELITES. SEE PLANS.
 B)SINGLE HUNG WINDOWS. IMPACT.
 C)ALL STRUCTURAL CONNECTORS.
 D)CONNECTORS WITHOUT PRODUCT APPROVAL
 STILL REQUIRE ONE. LETTER BY ARCHITECT
 ISN'T SUFFICIENT. STILL NEEDS COMPLETE
 INFORMATION FOR FLORIDA/LOCAL PRODUCT
 APPROVAL.
 E)FIXED WINDOW (IMPACT) WITH SIZE AS
 SPECIFIED AT KITCHEN AND DINING AREA.
 F)NEED FRENCH DOORS WITH SIDELITES AND
 TRANSOM ABOVE ASSEMBLY AS SHOWN ON
 PLANS. DETAIL SHOWN ON SHEET A6 IS THE
 SAME INFO. FROM PRODUCT APPROVAL BUT
 IT DOESN'T SPECIFY HOW IS THE ASSEMBLY
 PUT TOGETHER. INCLUDINGHEADER SPECS
 AND ATTACHMENT TO SIDE COLUMNS, AND
 DOORS AND TRANSOM ATTACHMENT TO HEADER
 4-PROVIDE COMPLETE DETAIL FOR STRUCTURAL
 FACIA TO SUPPORT TRUSSES AT REAR PORCH
 SINCE THERE ISN'T BEAM TO SUPPORT THEM
 SEC. 104.2.1.2 CITY AMENDMENTS TO FBC.
 5-SPECIFY CONNECTOR FOR BEAMS RESTING
 ON MASONRY WALL AT ENTRY PORCH. SEE
 ROOF FRAMING PLAN. SECTION 104.2.1.2
 CITY AMENDMENTS TO FBC 2001.