Plan Review Notes
Plan Review Notes For Permit 04011308
Permit Number 04011308
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-06 00:00:00**************** UNSAT *********
  
  
 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE
 CONDUCTOR ATTACHED TO NEW FOOTER STEEL.
 250.50
  
 2)NOTE: PLEASE VERIFY KW RATING/LOAD
 SHOWN FOR AHU. 6.5KW IS NOT A STANDARD
 SIZE.
  
 3)NOTE: PLEASE INCLUDE ALL REQ'D INFOR-
 -MATION ON TITLE BLOCK AS SET FORTH
 IN FAC 61G1-16.004 PER FS 481
  
 4)NOTE: PLEASE SEE KW LOAD SHOWN FOR
 WATER HEATER AT 2.5 KW. PLEASE ALSO
 VERIFY.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  