| Notes |
| Date |
Text |
| 2004-02-06 00:00:00 | **************** UNSAT ********* | | | | | | | | | 1)NOTE: PLEASE SHOW GROUNDING ELECTRODE | | | CONDUCTOR ATTACHED TO NEW FOOTER STEEL. | | | 250.50 | | | | | | 2)NOTE: PLEASE VERIFY KW RATING/LOAD | | | SHOWN FOR AHU. 6.5KW IS NOT A STANDARD | | | SIZE. | | | | | | 3)NOTE: PLEASE INCLUDE ALL REQ'D INFOR- | | | -MATION ON TITLE BLOCK AS SET FORTH | | | IN FAC 61G1-16.004 PER FS 481 | | | | | | 4)NOTE: PLEASE SEE KW LOAD SHOWN FOR | | | WATER HEATER AT 2.5 KW. PLEASE ALSO | | | VERIFY. | | | | | | PLEASE SUBMIT THE ABOVE INFORMATION FOR | | | REVIEW. IF THERE ARE ANY QUESTIONS, | | | PLEASE DO NOT HESITATE TO CALL. | | | | | | DEWEY PALMER | | | ELECTRICAL PLAN REVIEW | | | CITY OF WEST PALM BEACH | | | CONSTUCTION SERVICES DEPT. | | | 561-805-6717 | | | [email protected] |
|