| Plan Review Notes For Permit 04011300 |
| Permit Number |
04011300 |
|
| Review Stop |
E |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2004-03-25 00:00:00 | | | | UNSAT | | | ~~~~~ | | | ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~` | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | | REVIEW. | | | | | | 1} PLEASE SUBMIT AIC RATINGS FOR | | | ALL NEW SERVICE EQUIPMENT BEING | | | INSTALLED. MAINS/BRKRS AND PANELS ARE | | | ALL TO BE RATED FOR THE AVAILABLE FAULT | | | CURRENT. | | | PER 110.9/215.5 | | | | | | 2} THE FEEDERS ON THE RISER DIAGRAM | | | LISTED AT #00 ARE NOT RECOGNIZED AS AWG | | | PER 110.6. SEE 310.16 OR 310.15(B)(6) | | | FOR WIRE SIZE SELECTIONS. | | | | | | 3} THE WATER HEATER ON THE PANEL | | | SCHEDULE IS RATED AT 9000 WATTS, THE | | | WIRE SIZE @ #10 DOES NOT COMPLY WITH | | | 310.16. | | | | | | 4} THE TOTAL WATTAGE SHOWN FOR THE ARC | | | FAULT BREAKERS IS INCORRECT FOR THE OCP | | | AND WIRE SIZE LISTED FOR SAME. SEE | | | 310.16. | | | | | | 5} THE OCP FOR THE AC COMPRESSORS LISTED | | | @ 1200 WATTS(?) DOES NOT COMPLY WITH | | | 310.16. | | | | | | 6} THE SMOKE DETECTORS BY THE GARAGE AND | | | SECOND FLOOR BATH DO NOT COMPLY WITH | | | 8-1.4.2 NFPA-72, AS STATED IN THE | | | PREVIOUS REVIEW, THEY MUST BE A MINIMUM | | | OF 3'. | | | | | | BILL TROBAUGH | | | ELECTRICAL PLAN REVIEW | | | 561/805-6718 | | | [email protected] | | | FAX/:561/659-8026 |
|