Plan Review Notes
Plan Review Notes For Permit 04011300
Permit Number 04011300
Review Stop E
Sequence Number 2
Notes
Date Text
2004-03-25 00:00:00 
 UNSAT
 ~~~~~
 ~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~~`
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 1} PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING
 INSTALLED. MAINS/BRKRS AND PANELS ARE
 ALL TO BE RATED FOR THE AVAILABLE FAULT
 CURRENT.
 PER 110.9/215.5
  
 2} THE FEEDERS ON THE RISER DIAGRAM
 LISTED AT #00 ARE NOT RECOGNIZED AS AWG
 PER 110.6. SEE 310.16 OR 310.15(B)(6)
 FOR WIRE SIZE SELECTIONS.
  
 3} THE WATER HEATER ON THE PANEL
 SCHEDULE IS RATED AT 9000 WATTS, THE
 WIRE SIZE @ #10 DOES NOT COMPLY WITH
 310.16.
  
 4} THE TOTAL WATTAGE SHOWN FOR THE ARC
 FAULT BREAKERS IS INCORRECT FOR THE OCP
 AND WIRE SIZE LISTED FOR SAME. SEE
 310.16.
  
 5} THE OCP FOR THE AC COMPRESSORS LISTED
 @ 1200 WATTS(?) DOES NOT COMPLY WITH
 310.16.
  
 6} THE SMOKE DETECTORS BY THE GARAGE AND
 SECOND FLOOR BATH DO NOT COMPLY WITH
 8-1.4.2 NFPA-72, AS STATED IN THE
 PREVIOUS REVIEW, THEY MUST BE A MINIMUM
 OF 3'.
  
 BILL TROBAUGH
 ELECTRICAL PLAN REVIEW
 561/805-6718
 [email protected]
 FAX/:561/659-8026