| 2004-02-09 00:00:00 | **************** UNSAT *************** |
| | |
| | 1)NOTE: SMOKE DETECTORS ARE REQUIRED |
| | INSIDE AND OUTSIDE ALL SLEEPING ROOMS. |
| | ON EACH LEVEL OF A MULTI-LEVEL DWELLING |
| | UNIT. |
| | IN CLOSE PROXIMITY OF STAIRWAYS LEADING |
| | TO FLOORS ABOVE AND IN THE VICINITY OF |
| | BEDROOMS. |
| | PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE |
| | A MIN OF 3' FROM BATHROOM DOORS AND |
| | KITCHENS. |
| | ABOVE PER:FBC 905.2, NFPA-72 8-1.4 |
| | |
| | 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR |
| | ALL NEW SERVICE EQUIPMENT BEING INSTALL- |
| | ED. MAINS/BRKRS AND PANELS ARE ALL TO BE |
| | RATED FOR THE AVAILABLE FAULT CURRENT. |
| | PER 110.9/215.5 |
| | |
| | 3)NOTE: PLEASE SEE SEC'S AND FEEDERS |
| | SHOWN AT #00. PLEASE SEE AWG STANDARD |
| | SIZES IN NEC 310.16. 3/0'S? |
| | |
| | 4)NOTE: PERMIT APPLICATION IS FOR A NEW |
| | 2-STORY RES. HOWEVER, RISER DIAGRAM NOTE |
| | -S BEING EXISTING. PANEL SCHEDULE NOTES |
| | NEW AND EXISTING??? PLEASE CLARIFY THIS? |
| | |
| | 5)NOTE: PLEASE SIZE SIZING OF CONDUIT |
| | FOR 3-3/0'S AND AN EQUIPMENT GROUNDING |
| | CONDUCTOR REQ'D FROM MAIN TO PANEL. |
| | CONDUIT SHOWN AS 1 1/2". |
| | PLEASE ALSO SEE THAT LOCATION OF PANEL |
| | IS NOT SHOWN ON PLANS AND THEREFORE |
| | MAIN MAY OR MAY NOT BE REQ'D. |
| | PLEASE SEE LOCAL AMENDMENTS, 210.70 |
| | NO MORE THAN 8' OF UNPROTECTED CONDUCTOR |
| | -S ARE PERMITTED INSIDE THE HOUSE. |
| | |
| | 6)NOTE: PLEASE LIST ALL THE REQ'D ARC |
| | FAULT PROECTED CIRCUITS ON PANEL SCHED- |
| | -ULE. PER 210.12 2002 NEC |
| | |
| | 7)NOTE: PLEASE SEE PLANS ON A-10 REF |
| | ELECTRICAL CODE PER SEC .2701?? |
| | PLEASE SEE THAT PLANS ARE PER 2002 NEC. |
| | |
| | 8)NOTE: PLEASE SEE MISSING FRONT AND |
| | REAR RECEPTS PER 210.52E. |
| | |
| | 9)NOTE: PLEASE SEE REQ'D MISSING EGRESS |
| | LIGHTING AND MEANS OF CONTROL PER 210.70 |
| | AND LS 101 5-8 |
| | |
| | 10)NOTE: PLEASE CLARIFY CORNER IN WHICH |
| | KITCHEN COUNTER TOP INTERSECTS WITH |
| | PENINSULAR? IS THIS COUNTERSPACE OR AN |
| | EMPTY CORNER? PLEASE SEE 210.52C1 FOR |
| | RECEPT SPACING IF COUNTER-TOP. |
| | |
| | 11)NOTE: PLEASE SHOW ALL RECEPTS SERVING |
| | KITCHEN COUNTERSPACE AS GFI/GFI PROTECT- |
| | -ED PER 210.8A6 THIS INCLUDES RECEPT |
| | SERVING PENINSULAR. |
| | |
| | 12)NOTE: PLEASE SEE MISSING RECEPT(S) |
| | FOR BATHROOM(S) PER 210.52D AND LIST |
| | PER 210.11C3. MUST BE DEDICATED, 20A AND |
| | #12. |
| | |
| | 13)NOTE: PLEASE SEE MISSING RECEPT FOR |
| | A/C EQUIPMENT. PER 210.63 |
| | PLANS ONLY SHOW ONE AHU IN ATTIC ON 2ND |
| | FLOOR. PLEASE SHOW 2ND UNIT. DISC'S TO |
| | BE SHOWN PER 440.11 |
| | |
| | 14)NOTE: PLANS THAT CONTAIN A TITLE |
| | BLOCK FOR AND ENGINEER OR ARCH MUST BE |
| | SIGNED, DATED AND SEALED BY THE DESIGNER |
| | OF RECORD. PER FS 471.025 AND 481.221 |
| | |
| | |
| | PLEASE SEE THAT PLANS DO NOT CONTAIN |
| | ANY LOW VOLTAGE ITEMS. (TV,PHONE ETC) |
| | PLEASE SHOW AT THIS TIME OR SEPARATE |
| | PLANS WILL BE REQ'D WITH LV PERMIT |
| | APPLICATION. |
| | |
| | PLEASE SUBMIT THE ABOVE INFORMATION FOR |
| | REVIEW. IF THERE ARE ANY QUESTIONS, |
| | PLEASE DO NOT HESITATE TO CALL. |
| | |