Plan Review Notes
Plan Review Notes For Permit 04011300
Permit Number 04011300
Review Stop E
Sequence Number 1
Notes
Date Text
2004-02-09 00:00:00**************** UNSAT ***************
  
 1)NOTE: SMOKE DETECTORS ARE REQUIRED
 INSIDE AND OUTSIDE ALL SLEEPING ROOMS.
 ON EACH LEVEL OF A MULTI-LEVEL DWELLING
 UNIT.
 IN CLOSE PROXIMITY OF STAIRWAYS LEADING
 TO FLOORS ABOVE AND IN THE VICINITY OF
 BEDROOMS.
 PLEASE ALSO NOTE, SD'S ARE REQ'D TO BE
 A MIN OF 3' FROM BATHROOM DOORS AND
 KITCHENS.
 ABOVE PER:FBC 905.2, NFPA-72 8-1.4
  
 2)NOTE: PLEASE SUBMIT AIC RATINGS FOR
 ALL NEW SERVICE EQUIPMENT BEING INSTALL-
 ED. MAINS/BRKRS AND PANELS ARE ALL TO BE
 RATED FOR THE AVAILABLE FAULT CURRENT.
 PER 110.9/215.5
  
 3)NOTE: PLEASE SEE SEC'S AND FEEDERS
 SHOWN AT #00. PLEASE SEE AWG STANDARD
 SIZES IN NEC 310.16. 3/0'S?
  
 4)NOTE: PERMIT APPLICATION IS FOR A NEW
 2-STORY RES. HOWEVER, RISER DIAGRAM NOTE
 -S BEING EXISTING. PANEL SCHEDULE NOTES
 NEW AND EXISTING??? PLEASE CLARIFY THIS?
  
 5)NOTE: PLEASE SIZE SIZING OF CONDUIT
 FOR 3-3/0'S AND AN EQUIPMENT GROUNDING
 CONDUCTOR REQ'D FROM MAIN TO PANEL.
 CONDUIT SHOWN AS 1 1/2".
 PLEASE ALSO SEE THAT LOCATION OF PANEL
 IS NOT SHOWN ON PLANS AND THEREFORE
 MAIN MAY OR MAY NOT BE REQ'D.
 PLEASE SEE LOCAL AMENDMENTS, 210.70
 NO MORE THAN 8' OF UNPROTECTED CONDUCTOR
 -S ARE PERMITTED INSIDE THE HOUSE.
  
 6)NOTE: PLEASE LIST ALL THE REQ'D ARC
 FAULT PROECTED CIRCUITS ON PANEL SCHED-
 -ULE. PER 210.12 2002 NEC
  
 7)NOTE: PLEASE SEE PLANS ON A-10 REF
 ELECTRICAL CODE PER SEC .2701??
 PLEASE SEE THAT PLANS ARE PER 2002 NEC.
  
 8)NOTE: PLEASE SEE MISSING FRONT AND
 REAR RECEPTS PER 210.52E.
  
 9)NOTE: PLEASE SEE REQ'D MISSING EGRESS
 LIGHTING AND MEANS OF CONTROL PER 210.70
 AND LS 101 5-8
  
 10)NOTE: PLEASE CLARIFY CORNER IN WHICH
 KITCHEN COUNTER TOP INTERSECTS WITH
 PENINSULAR? IS THIS COUNTERSPACE OR AN
 EMPTY CORNER? PLEASE SEE 210.52C1 FOR
 RECEPT SPACING IF COUNTER-TOP.
  
 11)NOTE: PLEASE SHOW ALL RECEPTS SERVING
 KITCHEN COUNTERSPACE AS GFI/GFI PROTECT-
 -ED PER 210.8A6 THIS INCLUDES RECEPT
 SERVING PENINSULAR.
  
 12)NOTE: PLEASE SEE MISSING RECEPT(S)
 FOR BATHROOM(S) PER 210.52D AND LIST
 PER 210.11C3. MUST BE DEDICATED, 20A AND
 #12.
  
 13)NOTE: PLEASE SEE MISSING RECEPT FOR
 A/C EQUIPMENT. PER 210.63
 PLANS ONLY SHOW ONE AHU IN ATTIC ON 2ND
 FLOOR. PLEASE SHOW 2ND UNIT. DISC'S TO
 BE SHOWN PER 440.11
  
 14)NOTE: PLANS THAT CONTAIN A TITLE
 BLOCK FOR AND ENGINEER OR ARCH MUST BE
 SIGNED, DATED AND SEALED BY THE DESIGNER
 OF RECORD. PER FS 471.025 AND 481.221
  
  
 PLEASE SEE THAT PLANS DO NOT CONTAIN
 ANY LOW VOLTAGE ITEMS. (TV,PHONE ETC)
 PLEASE SHOW AT THIS TIME OR SEPARATE
 PLANS WILL BE REQ'D WITH LV PERMIT
 APPLICATION.
  
 PLEASE SUBMIT THE ABOVE INFORMATION FOR
 REVIEW. IF THERE ARE ANY QUESTIONS,
 PLEASE DO NOT HESITATE TO CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]