| Notes |
| Date |
Text |
| 2005-01-06 00:00:00 | ****CORRECTIONS**** | | | TRUSS ENGINEERING | | | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | | [email protected] | | | | | | 1.)THERE IS A NOTE FROM YOU DOR ON | | | YOUR PLAN THAT EOR IS TO REVIEW | | | STRAPPING (SHEET 10).PLEASE HAVE | | | REVIEWED BEFORE RESUBMITTAL. | | | | | | 2.)THE NEW TRUSS CALCS, ROOF, SHOW A | | | STRESS INCREASE OF 1.25 FOR THE TRUSSES | | | AND FOR THE PLATES.STRESS INCREASE FOR | | | STEEL IS NOT PERMITTED FBC1609.4.3(2). | | | | | | 3.)DOR HAS SPECIFIED A ROOF LIVE LOAD | | | OF 30; TRUSS DRAWINGS SHOW 20. | | | | | | 4.)INDEX SHEET SHOWS THE WRONG | | | ADDRESS.THIS JOB IS NOT IN BOCA RATON. | | | SECOND TIME THIS CORRECTION HAS BEEN | | | MADE. | | | | | | |
|