2004-12-29 00:00:00****CORRECTIONS****
 TRUSS SUBMITTAL
 2ND REVIEW
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 [email protected]
  
 1.)SEE PREVIOUS LIST.ATTICS ARE IN
 THE ROOF, NOT THE FLOOR.BOTTOM CHORD
 LIVE LOAD IS TO BE 10 FOR ATTICS WITH NO
 STORAGE, 30 FOR ATTICS WITH STORAGE FBC
 TABLE 1604.1.
  
 2.)FLOOR TRUSS TOTAL LOAD SHOWN ON THE
 INDEX PAGE IS NOT CORRECT.40+10+10+10
 EQUALS 70, NOT 65.
  
 3.)PROJECT NAME AND ADDRESS ON THE
 INDEX SHEET IS INCORRECT.I ASSUME THAT
 THIS IS THE SUBCONTRACTOR; SHOULD BE THE
 PROJECT NAME AND ADDRESS.IF THIS IS
 THE PROJECT, WRONG JOB - STATES 105
 BEVERLY ROAD, BOCA RATON.
  
 4.)SOME OF THE DETAILS PROVIDED SHOULD
 EITHER BE SEALED OR REFERENCED ON THE
 INDEX SHEET.NOTE THAT THE INDEX SHEET
 DOES NOT REFER TO ALL SHEETS IN THE
 PACKAGE.